<(760) User operation setting>
Line of 11 points curves defined by customer is set by operating
actuator position.
Procedure
LCD display
1
Hold down the set button ( )
for 1sec. or longer to start
parameter change mode.
2
Select (USEr) with the UP or
DOWN button ( ) and hold
down the set button ( ) for
1sec. or longer.
3
Select (ACT) for value setting, and
hold down the set button ( )
for 1sec. or longer.
4
Hold down the set button ( )
for 1sec. or longer with specified
input current parameter.
5
The LCD displays go (Go) for
confirmation. Confirm there are no
hazardous conditions due to the
actuator startup, and then hold
down the set button ( ) for
1sec. or longer.
6
Operate the actuator by pressing
UP or DOWN button ( ).
Check the actuator movement, and
hold down the mode button ( ) at
desired position for 1sec.
7
Pressing UP or DWON button
( ), and set input current
parameter of 10 points as clause 4
to 6.
8
Hold down the mode button ( )
again for 1sec. or longer for 3 times
with some interval.