No.IP8S-OM00009
46
<
(430) Operation setting
*21
>
Set stroke for 0% and 100% of input signal by operating the
actuator.
Procedure
LCD display
1
Hold down the set button ( )
for 1sec. or longer to move on to
parameter change mode.
2
Select Operation setting (Act) or
non zero point / span mode (oFF)
by UP or DOWN button ( ).
3
To select
Operation setting (Act)
,
hold down the set button( )
for 1sec. or longer to go to value
change mode.
When selecting non
zero point / span mode (oFF), hold
down the mode button ( ) for
1sec. or longer to set the value.
4
<Hereafter, only when (ACt) is set>
Select (431) to set lower limit, and
hold down the set button ( )
for 1sec. or longer.
5
The LCD displays go (Go) for
confirmation. Confirm there are no
hazardous conditions due to the
actuator startup, and then press
and hold down the set button
(
+
) for 1sec. or longer
*9
.
6
Operate the actuator by pressing
UP or DOWN button ( ).
Check the actuator movement, and
hold down the mode button ( ) at
desired position for 1sec.
7
To set upper limit, press UP or
DOWN button ( ) and select
(432). For setting as lower limit
setting of clause 5, 6. Hold down
the mode button ( ) after changing
to set.
8
Hold down the mode button ( ) for
1sec. or longer. Hold down again
for 1sec. or longer after interval.
21: This function becomes applicable after initial adjustment is
completed.
+
or
+
+
or
or
A