No.IP8S-OM00009
45
<
(420) Ratio setting
>
Input all valve stroke which is used (incl. over travel), and select
over travel setting side.
Procedure
LCD display
1
Hold down the set button ( )
for 1sec. or longer to move on to
parameter change mode.
2
Select Ratio setting (rAtE) or non
zero point / span mode (oFF) by UP
or DOWN button ( ).
3
To select
Ratio setting (rAtE)
, hold
down the set button( ) for
1sec. or longer to go to value
change mode.
When selecting
non zero point / span mode (oFF),
hold down the mode button ( ) for
1sec. or longer to set the value.
4
<Hereafter, only when (rAtE) is set>
Select (st FULL) with UP or DOWN
button ( ), and hold down the
set button ( ) for 1sec. or
longer.
After
values
flashing,
change all actuator stroke within
0.0 to 999.9mm. Hold down the
mode button ( ) for 1 sec. or
longer for 2 times with some
interval.
5
After (st USE) is indicated, mode
move on to value change mode
automatically. As stroke setting
(412) of clause 4, set stroke within
0.0 to 999.8mm (60% or more of all
actuator stroke). After changing,
hold down the mode button ( ) for
1sec. or longer to set.
6
Press UP or DOWN button ( )
to select over travel setting side (st
SidE), then, hold down the set
button ( ) for 1sec. or longer.
7
Select 0% or 100% side with UP or
DOWN button. Hold down the
mode button ( ) after selection for
1sec. or longer to set.
8
Hold down the mode button ( ) for
1sec. or longer. Hold down again
for 1sec. or longer after interval.
+
or
+
+
or
or
+