![background image](http://html.mh-extra.com/html/smc-networks/inr-244-780/inr-244-780_operation-manual_1299957018.webp)
HEC-OM-S002
Chapter 3 Transporting and Installation
3.2 Installation
3-2
3.2 Installation
3.2.1 Installation
Conditions
z
Outdoor
z
Altitude higher than 2000m.
z
Environments containing splashing water, salt water, oil, or various
chemicals (including chemical mists).
z
Environments containing particles and dust.
z
Environments containing corrosive gas, solvents and flammable gas.
z
Envirnoments containing direct sunlight and radiant heat.
z
Environments having ambient temperatures over the following range:
Operation 10 to 35
o
C
Storage 0 to 50
o
C (with no liquid in the bath and facility water
circuit.)
z
Environments having ambient humidity over the following range:
Operation 35 to 80%
Storage 35 to 85%
z
Environments with sharp temperature changes.
z
Environments generating strong magnetic noise (having a strong electric
or magnetic field that generates surges).
z
Environments generating electrical static discharge and conditions in
which static electricity is applied to this product.
z
Environments generating strong high frequency radiation (including radio
frequency appliances such as mobile phones and tranceivers).
z
Environments generating strong vibrations and impacts.
z
Keep enough open space to access main power switch and any
cable connections.
z
Keep enough ventilation for liquid vapor.
z
This product should be installed on a vibration-free stable level
place.
z
The mounting orientation of this product is horizontal.
z
Place the product in a flat area which can handle its weight and
take measures to prevent the tipping of the product. If installed
improperly, the product might leak liquid or topple, resulting in
injury.
z
Do not use this product in the following environments, where the
product may not work normally and may be damaged.