8.4 Offset Function
HRZ Series
8-20
When MODE2 is selected
With OFFSET value set at -1°C, TEMP PV and communication data express
“29°C” (circulating fluid discharge temp. value + OFFSET value) that agrees with
the temperature of the circulating fluid in your system.
Figure 8-8 When MODE2 is selected
When MODE3 is selected
This mode enables this system to exercise temperature control to obtain 31°C
(TEMP SP value +OFFSET value), with OFFSET value set at 1°C. Once the
discharge temperature of the circulating fluid becomes 31°C, 1°C-thermal
dissipation is assured to allow the circulating fluid in your system to be 30°C.
TEMP SP value is obtained for your system. TEMP PV and communication data
also express “30°C” (circulating fluid discharge temp. value - OFFSET value) that
agrees with the temperature of the circulating fluid in your system.
Figure 8-9 When MODE3 is selected
1
℃
This system
Your system
Discharge temp.:
30
℃
Circulating fluid temp. in
your system: 29
℃
TEMP PV 29
℃
TEMP SP 30
℃
OFFSET -1
℃
External communication
Communication data
TEMP PV 29
℃
TEMP PV
29
℃
Heat dissipation:
Heat
1
℃
This system
Your system
Discharge temp:
31
℃
Circulating fluid temp. in
your system: 30
℃
TEMP PV 30
℃
TEMP SP 30
℃
OFFSET
1
℃
External communication
Communication data
TEMP PV 30
℃
TEMP PV
30
℃
dissipation: