HRX-OM-R039
Chapter 5 Display and setting of various functions
HRSE Series
5.4
Inspection monitor menu
5-11
Check of the accumulated operation time of the pump
8.
Press the [SEL] key once.
The accumulated operation time of the pump is displayed on the digital display.
PV
SV
Displays the accumulated operation time of the pump. Refer to the table below for the display.
Table 5.4-2 List of time display
Cumulative time
Indicated value
0h to
999h
to
1,000h to 99,999h
to
100,000h
Return to
AL28 Pump maintenance alarm is generated when the accumulated operation time of the
pump reaches 20,000 hours (
) or more. For details, refer to Chapter 6 Alarm
indication and trouble shooting.
Check of the accumulated operation time of the fan motor
9.
Press the [SEL] key once.
The accumulated operation time of the fun motor is displayed on the digital display.
PV
SV
Displays the accumulated operation time of the fan motor. Refer to Table 5.4-2 for the display.
AL29 Fan motor maintenance alarm is generated when the accumulated operation time of
the fan motor reaches 20,000 hours ( ) or more. For details, refer to Chapter 6
Alarm indication and trouble shooting.
Check of the accumulated operation time of the compressor
10.
Press the [SEL] key once.
The accumulated operation time of the compressor is displayed on the digital display.
PV
SV
Displays the accumulated operation time of the compressor. Refer to Table 5.4-2 for the
display.
AL30 Compressor maintenance alarm is generated when the accumulated operation time
of the compressor reaches 50,000 hours ( ) or more. For details, refer to
Chapter 6
Alarm indication and trouble shooting.
Check of the accumulated operation time
11.
Press the [SEL] key once.
The accumulated operation time is displayed on the digital display.
PV
SV
Displays the accumulated operation time. Refer to Table 5.4-2 for the display.