-53-
EX
※※
-OMR1012
When configuring the input and output data size, please ensure the following steps are taken;
•The minimum value of both the input and output data size is 2 bytes.
If the EX600 data size is 0 or 1byte, this must be set to 2 bytes.
•If the input or output size is an odd number, add 1 byte, to make it an even number of bytes.
The I/O map is shown with the following unit configuration as an example.
<Example 1>
Unit 0
Unit 1
End plate
DY
□
B
Digital output
unit
1 byte output
SEN5
SI unit
4 bytes output
Valve
Input data: None
Output data: (Unit 0) Digital output Unit (EX600-DY
□
B): 1 byte occupied
(Unit 1) SI Unit (EX600-SEN5): 4 bytes occupied
•When Diagnostic mode 0 is selected
Input data
Output data
Byte0 DY
□
B (Unit 0)
Output 0 to 7
Byte1
Padding data
Output 0 to 7
Byte2
Output 8 to 15
Byte3
Output 16 to 23
Byte4
SEN5 (Unit 1)
Output 24 to 31
Byte5
Padding data
Total
2 bytes
6 bytes
•When Diagnostic mode 1 is selected
Input data
Output data
Byte0
Diagnostic data byte0
DY
□
B (Unit 0)
Output 0 to 7
Byte1
Diagnostic data byte1
Output 0 to 7
Byte2
Diagnostic data byte2
Output 8 to 15
Byte3
Diagnostic data byte3
Output 16 to 23
Byte4
SEN5 (Unit 1)
Output 24 to 31
Byte5
Padding data
Total
4 bytes
6 bytes