•Digital output unit parameters
Parameter
setting
No.
Parameter
Definition
Item
Content
Default
setting
By
E.O.
By
W.S.
Enable Generates
an
error.
○
1
Output load
short circuit
detection
Generates error
per unit when the
short circuit of the
output device is
detected.
1
Disable
Does not generate an
error.
○
○
Auto
Error is automatically
cleared when the short
circuit is fixed.
○
2
Restart after
output load
short circuit
Restore the setting
of short circuit
detection error per
unit after the output
device short circuit
is cleared.
Manual
Even when the short
circuit is fixed, error is not
cleared until the power is
supplied again.
○
○
Enable Generates
an
error.
3
Open circuit
detection
Generates error
per channel when
the disconnection
of the output
device is detected.
Disable
Does not generate an
error.
○
○
○
Clear
Turn off the output
○
Hold
Hold the output
4
Output setting
during
communication
fault
2
Set output per
channel when
communication is
abnormal.
ForceON
Turn on the output
forcefully
○
○
Clear
Turn off the output
○
Hold
Hold the output
5
Output setting
during
communication
idling
2
3
Set output per
channel during
communication
idling.
ForceON
Turn on the output
forcefully
○
○
Enable
Generates an error.
Val: 1 to 65000
5
6
Output
ON/OFF
counter
Memorizes the
number of times
the output device is
ON. Generates
error per channel
when the operation
count exceeds the
set value.
4
Disable
Does not generate an
error.
○
○
○
7
Valve
ON/OFF
counter clear
Clears the valve
ON/OFF counter to
0. (Refer to page
method).
-
-
-
x
○
1: Could be incorrectly recognized as short circuit depending on used load (ex.: lamp load). If detection is incorrect, disable the
parameter setting.
2: This function is valid only when “Hold/Clear priority” of the system parameter is set to “Via software“.
3: Some PLC does not support an idle mode.
4: The count is memorized every hour. When the power supply is turned on again, counting starts from the last value memorized.
5: Times for setting is set value x1000 times.