EX
※※
-OMR1012
Output value during communication error (Fault Value)
Refer to the tables below for setting the Fault value via PLC.
•Set in decimal number.
•Conversion value varies depending on the assigned analogue data format and the analogue output range.
(1) Offset binary data format
•Range: 0 to 10 V, 0 to 5 V, 0 to 20 mA
•Range: 1 to 5V, 4 to 20 mA
Settable value
by PLC
(AD value)
Output signal range
(0 to b)
Voltage
[V]
Current
[mA]
Decimal
number
0 to 10
0 to 5
0 to 20
4095 10.5
5.25
21
3901 10 5 20
2048 5.25
2.625
10.5
0 0
0
0
Settable value
by PLC
(AD value)
Output signal range
(a to b)
Voltage
[V]
Current
[mA]
Decimal
number
1 to 5
4 to 20
4095 5.25
21
3868 5
20
2048 3
12
228 1
4
0 0.75
3
Example: To set the Fault value to 10 V when offset binary data format (analogue data format) and
range 0 to 10 V (analogue output range) are set, the value set to PLC is "3901" from the table
on the left.