PRODUCT NAME 

 

Fieldbus system 

EtherNet/IP

TM

 compatible SI Unit 

 

MODEL / Series / Product Number 

 

EX600-SEN5-X22 

EX600-ED# 

 
 
 

 

This manual is for Ford Motor Company. 
Any IP address within the 136.129.0.1 to 136.129.7.254 range can be set with a switch. 
This IP address range can only be used with the permission of Ford Motor Company. 

 
 
 
 
 
 
 
 
 

 

 

EX

※※

-OMR1012  

Summary of Contents for EX600 Series

Page 1: ...Unit MODEL Series Product Number EX600 SEN5 X22 EX600 ED This manual is for Ford Motor Company Any IP address within the 136 129 0 1 to 136 129 7 254 range can be set with a switch This IP address range can only be used with the permission of Ford Motor Company EX OMR1012 ...

Page 2: ...ification 26 Specifications 26 Dimensions 27 End Plate Model Indication and How to Order 28 Summary of Product parts 28 Mounting and Installation 29 Wiring 29 Specification 30 Specifications 30 Dimensions 30 Maintenance 32 Parameter Setting 33 Parameter definition and setting 33 I O Map 52 Diagnosis 56 Details of diagnostic data 57 Hardware Configuration 58 EDS file and icon 58 Setting using RSLog...

Page 3: ... equipment failure when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly The assembly operation and maintenance of machines or equipment including our products must be performed by an operator who is appropriately trained and experienced 3 Do not service or attempt to remo...

Page 4: ...y a replacement product or necessary parts will be provided This limited warranty applies only to our product independently and not to any other damage incurred due to the failure of the product 3 Prior to using SMC products please read and understand the warranty terms and disclaimers noted in the specified catalogue for the particular products 2 Vacuum pads are excluded from this 1 year warranty...

Page 5: ...ctric shock Do not operate the product outside of the specifications Do not use for flammable or harmful fluids Fire malfunction or damage to the product can result Verify the specifications before use Do not operate in an atmosphere containing flammable or explosive gases Fire or an explosion can result This product is not designed to be explosion proof If using the product in an interlocking cir...

Page 6: ...instructions on design and selection installation wiring environment adjustment operation maintenance etc described below must also be followed Product specifications The direct current power supply to combine should be UL1310 Class 2 power supply when conformity to UL is necessary Use the specified voltage Otherwise failure or malfunction can result The power supply for the unit should be 0V as t...

Page 7: ...proper insulation of wiring Poor insulation interference from another circuit poor insulation between terminals etc can lead to excess voltage or current being applied to the product causing damage Take appropriate measures against noise such as using a noise filter when the Fieldbus system is incorporated into equipment Otherwise noise can cause malfunction Environment Select the proper type of p...

Page 8: ...ment and Operation Set the switches by using a sharp pointed screwdriver etc When setting the switch do not touch other unrelated parts This can cause parts damage or malfunction due to a short circuit Perform settings suitable for the operating conditions Incorrect setting can cause operation failure Please refer to the PLC manufacturer s manual etc for details of programming and addresses For th...

Page 9: ... with switch output capability PNP and NPN types are available Digital output unit For connecting output device such as solenoid valves lamps buzzers etc PNP and NPN types are available Digital I O unit This unit has both digital input and output functions PNP and NPN types are available Analogue input unit For connecting sensors with analogue output capability Analogue output unit This can be con...

Page 10: ...address A unique number inherent to all devices which are connected to EtherNet IP TM M Manifold A form consisting of multiple components A form made by combining multiple components NPN input Takes the sensor output that uses the NPN transistor to the signal output line NPN output The output type that uses an NPN transistor to operate output device It is also known as a positive common type since...

Page 11: ...ssary 1 Connect the unit to the end plate The Digital unit Analogue unit can be connected in any order Tightening torque 1 5 to 1 6Nm 2 Add more units Up to 10 units including the SI unit can be connected to one manifold 3 Connecting the SI unit After connecting the necessary units connect the SI unit Connecting method is the same as above 1 2 ...

Page 12: ...00 3 places VQC4000 4 places SY 2 places 5 Connect the SI unit and the valve manifold Insert the valve plate to the valve plate set groove on the side of SI unit Then tighten it with the valve plate set screws M4 x 6 to fix the plate Tightening torque 0 7 to 0 8 Nm Precautions for handling Please do not connect the unit while the power supply is active It will cause equipment damage Take care not ...

Page 13: ...ediate reinforcing brace EX600 ZMB1 before mounting using 2 M4 x 5 screws Tightening torque 0 7 to 0 8 Nm Intermediate reinforcing brace EX600 ZMB1 2 Fix and tighten the end plates at one end of the unit M4 Tightening torque 0 7 to 0 8 Nm Fix the end plate at the valve side while referring to the operation manual of the corresponding valve manifold n Number of connected Units 10 ...

Page 14: ...t EX600 ZMA2 to the end plate at the opposite end to the valves using 2 M4 x 14 screws Tightening torque 0 7 to 0 8 Nm 3 Hook the DIN rail mounting groove to the DIN rail 4 Press the manifold using its side hooked to the DIN rail as a fulcrum until the manifold is locked 5 Fix the manifold by tightening the DIN rail fixing screws of the EX600 ZMA2 M4 x 20 Tightening torque 0 7 to 0 8 Nm The tighte...

Page 15: ...connector into the unit vertically If they are not aligned the connector cannot be joined properly 3 When the mark B of the connector has been turned 180 degrees 1 2 turn wiring is completed Confirm that the connection is not loose If turned too far it will become hard to remove the connector 1 2 3 Mounting the marker Signal name of the input or output devices and unit address can be written to th...

Page 16: ... OUT Connects the cable for fieldbus outputs M12 5 pin socket SPEEDCON 5 Marker groove Groove to mount a marker 6 Connector PCI Connects the cable of the handheld terminal M12 5 pin socket SPEEDCON 7 Valve plate mounting screw hole Fixes the valve plate 8 Valve plate mounting groove Groove to insert the valve plate into 9 Joint bracket Bracket for joining to adjacent units 10 Unit connector plug T...

Page 17: ... Connector pin assignment Configuration BUS IN BUS OUT Pin No Signal name 1 TX 2 RX 3 TX 4 RX Precautions for handling Be sure to fit a seal cap on any unused connectors Proper use of the seal cap enables the enclosure to achieve IP67 specification ...

Page 18: ...htening screw in the reverse order of the above procedure Tightening torque 0 3 to 0 4 Nm Precautions for handling Turn off the power supply whilst setting the switch If there is foreign matter or water droplets around the display cover clean it off before opening the cover When setting the switch do not touch other unrelated parts This can cause parts damage or malfunction due to a short circuit ...

Page 19: ...LEAR switch Sets the output status when the fieldbus has a communication error or is in idling state Settings1 1 Content OFF Output is OFF default setting ON Holds the output This switch can be enabled and disabled by parameter Switch for diagnosis Allocates the diagnostic data to the input data Settings1 2 Mode Content Diagnostic size set for the input OFF 0 Input data only default setting 0 byte...

Page 20: ...ON ON ON ON ON ON 192 168 1 254 255 255 255 0 ON OFF ON ON ON ON ON ON ON ON DHCP mode 1 ON OFF OFF OFF OFF OFF OFF OFF OFF OFF Remote Control mode 2 1 The mode to obtain IP address from DHCP server Obtained IP address etc is lost when the power supply is cut 2 The mode to respond to the commands below of BOOTP DHCP Server provided by Rockwell Automation Enable DHCP IP address etc can be obtained ...

Page 21: ...ieldbus has a communication error or is in idling state Settings1 4 Content OFF Output is OFF default setting ON Holds the output This switch can be enabled and disabled by parameter Switch for diagnosis Allocates the diagnostic data to the input data Settings1 8 Mode Content Diagnostic size set for the input OFF 0 Input data only default setting 0 byte ON 1 Input data System diagnosis Unit diagno...

Page 22: ...F OFF 136 129 7 1 ON ON ON OFF ON ON ON ON ON ON ON 136 129 7 254 255 255 248 0 ON OFF ON OFF ON OFF ON ON ON ON ON ON ON ON DHCP mode 1 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF Remote Control mode 2 1 The mode to obtain IP address from DHCP server Obtained IP address etc is lost when the power supply is cut 2 The mode to respond to the commands below of BOOTP DHCP Server provided by Rockwell A...

Page 23: ...ethod of IP address by BOOTP DHCP Server When BOOTP DHCP Server starts up the Server scans the devices connected to the network After selecting the MAC address of EX600 IP address is set IP address is set and added to the list ...

Page 24: ...he communication status of the BUS OUT side SI unit common status LED display Content OFF The power supply for control and input is Off Green LEDs are ON The unit is in normal operation Red ST M LED is ON The element in SI unit is broken Red PWR LED is ON The power supply voltage for control and input is abnormal Red PWR V LED is ON The power supply voltage for output is abnormal Green ST M LED is...

Page 25: ...nit is in normal operation Red MS LED is flashing Recoverable error Red MS LED is ON The element in SI unit is broken Network status LED display Content NS LED is OFF The power supply for control and input is OFF or IP address is not set Green NS LED is flashing The unit received an IP address but connection is not established Green NS LED is ON Connection is established Red NS LED is flashing Con...

Page 26: ...N side Link Activity 100 Mbps Yellow ON Bus IN side Link No Activity 10 Mbps Yellow flashing Bus IN side Link Activity 10 Mbps OFF Bus OUT side No Link No Activity Green ON Bus OUT side Link No Activity 100 Mbps Green flashing Bus OUT side Link Activity 100 Mbps Yellow ON Bus OUT side Link No Activity 10 Mbps Yellow flashing Bus OUT side Link Activity 10 Mbps ...

Page 27: ...ported Applicable valve series Solenoid valve with surge voltage suppressor 24 VDC 1 0 W or less SMC Valve output Max number of solenoid valves 32 outputs PNP Negative common Operating temperature range 10 to 50 o C Storage temperature range 20 to 60 o C Operating humidity range 35 to 85 RH no dew condition Withstand voltage 500 VAC for 1 minute between external terminals and FE Insulation resista...

Page 28: ... 27 EX OMR1012 Dimensions ...

Page 29: ...n Summary of Product parts EX600 ED2 EX600 ED3 No Description Function 1 Power connector Connector for power supply to SI unit and I O unit 2 Fixing hole for direct mounting Holes for direct mounting 3 DIN rail fixing hole Holes for fix DIN rail mounting 4 F E terminal Functional Earth terminal must be connected directly to system earth ground 5 Connector Not used Unused connector Do not remove se...

Page 30: ...supply The power supply consists of two power supply systems as follows Power supply for control and input Supplying power for control of each unit s power supply for control and also for device connected to input port of Digital and Analogue unit Power supply for output Supplying power for equipment connected to output port of Digital and Analogue unit and also power supply for solenoid valve man...

Page 31: ...Enclosure IP67 With manifold assembled Operating temperature range 10 to 50 o C Storage temperature range 20 to 60 o C Operating humidity range 35 to 85 R H No condensation Withstand voltage 500 VAC for 1 minute between external terminals and F E Environment Insulation resistance 500 VDC 10 M min between external terminals and F E Standard CE marking UL CSA RoHS Weight 170 g 175 g All unused conne...

Page 32: ... 31 EX OMR1012 EX600 ED3 ...

Page 33: ...ing Connect properly if the connection is loose Seal cap Tighten properly if the connection is loose Thread for mounting and installation If the thread is loose re tighten it to the specified torque Connection cables If the cable is broken or any other abnormality is confirmed by appearance replace the cable with a new one Supply source voltage Check if source voltage within the specification rang...

Page 34: ...it switch becomes valid OFF Hold Forced ON can be set per channel 1 Hold Clear priority setting Switch the setting of the output during communication error or communication idling to follow the setting of the SI unit or the parameters Via software Setting by EtherNet IPTM object or the Web server becomes valid OFF Hold Forced ON can be set per channel LSB MSB The data format of all analogue units ...

Page 35: ... Does not generate an error Auto Error is automatically cleared when the short circuit is fixed 4 Restart after short circuit Restore the setting of short circuit detection error per unit after the valve short circuit is cleared Manual Even when the short circuit is fixed error is not cleared until the power is supplied again Enable Generates an error 5 Open Circuit Detection Generates error per c...

Page 36: ...t setting Sets the communication speed and communication method of BUS IN for the unit 100 FDX Selects the required communication speed and communication method Auto 10 HDX 10 FDX 100 HDX 11 BUS OUT port setting Sets the communication speed and communication method of BUS OUT for the unit 100 FDX Selects the required communication speed and communication method 1 This function is valid only when H...

Page 37: ...the input signal per unit 200 ms Selects the time to hold the input signal 15 ms Enable Generates an error Val 1 to 65000 4 6 Channel ON OFF counter Memorizes the number of times the input device is ON Generates error per channel when the operation count exceeds the set value 3 Disable Does not generate an error 7 Valve ON OFF counter clear Clears the valve ON OFF counter to 0 Refer to page 77 for...

Page 38: ...ation fault 2 Set output per channel when communication is abnormal ForceON Turn on the output forcefully Clear Turn off the output Hold Hold the output 5 Output setting during communication idling 2 3 Set output per channel during communication idling ForceON Turn on the output forcefully Enable Generates an error Val 1 to 65000 5 6 Output ON OFF counter Memorizes the number of times the output d...

Page 39: ...rates an error 5 Output load short circuit detection Generates error per unit when the short circuit of the output device is detected 1 Disable Does not generate an error Auto Error is automatically cleared when the short circuit is fixed 6 Restart after output load short circuit Restore the setting of short circuit detection error per unit after the output device short circuit is cleared Manual E...

Page 40: ...te an error 11 Valve ON OFF counter clear Clears the valve ON OFF counter to 0 Refer to page 77 for the clear method x 1 Could be incorrectly recognized as short circuit depending on used load ex lamp load If detection is incorrect disable the parameter setting 2 This function is valid only when Hold Clear priority of the system parameter is set to Via software 3 Some PLC does not support an idle ...

Page 41: ...rage filter Sets analogue filtering time per channel Sampling interval is approx 2 sec 8AVG 8 value average Enable Generates an error 5 Over range detection Generates error per unit when the input value exceeds 0 5 of full span Disable Does not generate an error Enable Generates an error 6 Under range detection Generates error per unit when the input value falls below 0 5 of full span Disable Does...

Page 42: ... 5 V 0 to 525 32768 to 33293 0 00 to 5 25 V 0 00 to 5 25 V 20 20 mA 0 to 2100 32768 to 34868 0 00 to 21 00 mA 0 00 to 21 00 mA 0 10 V 0 to 1050 0 00 to 10 50 V 0 5 V 0 to 525 0 00 to 5 25 V 1 5 V 75 to 525 0 75 to 5 25 V 0 20 mA 0 to 2100 0 00 to 21 00 mA 4 20 mA 300 to 2100 3 00 to 21 00 mA Follow the methods below when assigning the user set upper and lower limit by PLC Assigning positive value ...

Page 43: ...limit error Generates error per channel when the output value exceeds the set value Disable Does not generate an error Enable Generates an error Val 32766 to 32767 4 Scale upper limit setting Sets the scale upper limit Generates error per channel when the output value exceeds the upper limit Disable Does not generate an error Val 32766 to 32767 Val 1000 Enable Generates an error 1 User setting val...

Page 44: ...nd Fault Value User set output value Settable range Range Lower limit Upper limit Settable range during communication error or idling 0 10 V 0 00 to 10 45 V 0 05 to 10 50 V 0 00 to 10 50 V 0 5 V 0 00 to 5 22 V 0 03 to 5 25 V 0 00 to 5 25 V 1 5 V 0 75 to 5 22 V 0 78 to 5 25 V 0 75 to 5 25 V 0 20 mA 0 00 to 20 90 mA 0 10 to 21 00 mA 0 00 to 21 00 mA 4 20 mA 3 00 to 20 90 mA 3 10 to 21 00 mA 3 00 to ...

Page 45: ...0 mA Settable value by PLC AD value Output signal range 0 to b Voltage V Current mA Decimal number 0 to 10 0 to 5 0 to 20 4095 10 5 5 25 21 3901 10 5 20 2048 5 25 2 625 10 5 0 0 0 0 Settable value by PLC AD value Output signal range a to b Voltage V Current mA Decimal number 1 to 5 4 to 20 4095 5 25 21 3868 5 20 2048 3 12 228 1 4 0 0 75 3 Example To set the Fault value to 10 V when offset binary d...

Page 46: ...10 0 to 5 0 to 20 2047 10 5 5 25 21 1950 10 5 20 1024 5 25 2 625 10 5 0 0 0 0 Settable value by PLC AD value Output signal range a to b Voltage V Current mA Decimal number 1 to 5 4 to 20 2047 5 25 21 1934 5 20 1024 3 12 114 1 4 0 0 75 3 Example To set the Fault value to 10 V when signed binary data format analogue data format and range 0 to 10 V analogue output range are set the value set to PLC i...

Page 47: ...utput 3000 3 V output 4000 4 V output 5000 5 V output 3 The resolution from 1 to 5 V is 1 1000 based on the calculation 5 V 1 V 5000 1000 1 1000 Settable value by PLC AD value Output signal range a to b Voltage V Current mA Decimal number 0 to 10 1 to 5 0 to 5 0 to 20 4 to 20 Scale upper limit 32766 to 32767 10 5 5 20 20 Scale lower limit 32767 to 32766 0 1 0 0 4 If the data format is scaled data ...

Page 48: ... conversion type None None 2AVG 2 value average 4AVG 4 value average 4 Analogue average filter Sets analogue filtering time per channel Sampling interval is approx 2 sec 8AVG 8 value average Enable Generates an error 5 Over range detection Generates error per unit when the input value exceeds 0 5 of full span Disable Does not generate an error Enable Generates an error 6 Under range detection Gene...

Page 49: ...ate an error Val 32767 to 32766 Val 0 Enable Output will be user fault value 1 9 Output setting for communication fault 2 Set output per channel when communication is abnormal Disable Output will be held last state Enable Output will be user idle value 1 10 Output setting for communication idling 2 3 Sets output per channel during communication idling Disable Output will be held last state 1 Set v...

Page 50: ... 21 00 mA 0 00 to 21 00 mA 4 20 mA 3 00 to 20 90 mA 3 10 to 21 00 mA 3 00 to 21 00 mA Table User set values PLC Range Settable value by PLC Offset Binary Signed Magnitude 2 s Complement Expected value 0 10 V 0 to 1050 0 00 to 10 50 V 0 5 V 0 to 525 0 00 to 5 25 V 1 5 V 75 to 525 0 75 to 5 25 V 0 20 mA 0 to 2100 0 00 to 21 00 mA 4 20 mA 300 to 2100 3 00 to 21 00 mA If the data format is scaled data...

Page 51: ... 20 mA Settable value by PLC AD value Output signal range 0 to b Voltage V Current mA Decimal number 0 to10 0 to 5 0 to 20 4095 10 5 5 25 21 3901 10 5 20 2048 5 25 2 625 10 5 0 0 0 0 Settable value by PLC AD value Output signal range a to b Voltage V Current mA Decimal number 1 to 5 4 to 20 4095 5 25 21 3868 5 20 2048 3 12 228 1 4 0 0 75 3 Example To set the Fault value to 10 V when offset binary ...

Page 52: ...ut signal range a to b Voltage V Current mA Decimal number 1 to 5 4 to 20 2047 5 25 21 1934 5 20 1024 3 12 114 1 4 0 0 75 3 Example To set the Fault value to 10 V when signed binary data format analogue data format and range 0 to 10 V analogue output range are set the value set to PLC is 1950 from the table on the left 3 Scaled data format If the data format is scaled data format set the data as f...

Page 53: ... 4 EX600 DX B 8 inputs 1 0 EX600 DX C 8 inputs 1 0 EX600 DX C1 8 inputs with open circuit detection 1 0 EX600 DX D 16 inputs 2 0 EX600 DX E 16 inputs 2 0 Digital input unit EX600 DX F 16 inputs 2 0 EX600 DY B 8 outputs 0 1 EX600 DY E 16 outputs 0 2 Digital output unit EX600 DY F 16 outputs 0 2 EX600 DM E 8 inputs 8 outputs 1 1 Digital I O unit EX600 DM F 8 inputs 8 outputs 1 1 Analogue input Unit ...

Page 54: ...es output Valve Input data None Output data Unit 0 Digital output Unit EX600 DY B 1 byte occupied Unit 1 SI Unit EX600 SEN5 4 bytes occupied When Diagnostic mode 0 is selected Input data Output data Byte0 DY B Unit 0 Output 0 to 7 Byte1 Padding data Output 0 to 7 Byte2 Output 8 to 15 Byte3 Output 16 to 23 Byte4 SEN5 Unit 1 Output 24 to 31 Byte5 Padding data Total 2 bytes 6 bytes When Diagnostic mo...

Page 55: ... analogue value LSB MSB are selected Input data Output data Byte0 Lo byte DY B Unit 1 Output 0 to 7 Byte1 AXA channel 0 Unit 0 Hi byte DY B Unit 2 Output 0 to 7 Byte2 Lo byte Output 0 to 7 Byte3 AXA channel 1 Unit 0 Hi byte Output 8 to 15 Byte4 DX B Unit 3 Input 0 to 7 Output 16 to 23 Byte5 Input 0 to 7 SEN5 Unit 5 Output 24 to 31 Byte6 DX D Unit 4 Input 8 to 15 Byte7 Padding data Total 8 bytes 6 ...

Page 56: ... Input 0 to 7 Byte9 Input 0 to 7 Byte10 DX D Unit 4 Input 8 to 15 Byte11 Padding data Total 12 bytes 6 bytes When Diagnostic mode 1 and byte order of analogue value MSB LSB are selected Input data Output data Byte0 Diagnostic data byte0 DY B Unit 1 Output 0 to 7 Byte1 Diagnostic data byte1 DY B Unit 2 Output 0 to 7 Byte2 Diagnostic data byte2 Output 0 to 7 Byte3 Diagnostic data byte3 Output 8 to 1...

Page 57: ...switch the diagnostic data shown below is assigned to the head of input data of the I O map Refer to Setting and adjustment for setting the switch Mode Diagnostic data Diagnostic size 0 No diagnostic data 0 byte 1 System diagnosis Unit diagnosis 4 bytes ...

Page 58: ...output device is outside of the specification 1 The power supply voltage for control and input device is outside of the specification 2 Reserved 3 There is a connection failure between each unit During operation 4 There is a connection failure between each unit When the power supply is applied 5 Reserved 6 System error occurred 1 7 Hardware error occurred 0 There is an error in unit 0 1 There is a...

Page 59: ...figure EDS file ex600_sen_2p_qc2_v10 eds Icon ex600_1 ico Setting using RSLogix5000TM When connecting EX600 series use RSLogix5000TM software by Rockwell Automation Refer to the manual of RSLogix5000TM for a detailed manner of operation The screen data shown here is the English version of RSLogix5000 TM Select EtherNet IPTM module in I O Configuration folder Select New Module ...

Page 60: ... 59 EX OMR1012 Select Module window is displayed Select ETHERNET MODULE Generic Ethernet Module and click on OK ...

Page 61: ...nce Set as below Description Decimal Common Format Data INT Data SINT Input 100 100 Output 150 150 Configuration 105 105 5 Size Set as below Description Decimal Common Format Data INT Data SINT Input MIN 1 word MAX 32 words MIN 2 bytes MAX 64 bytes Output MIN 1 word MAX 32 words MIN 2 bytes MAX 64 bytes Configuration 0 word 0 byte Select the setting depending on the existence of diagnostic data an...

Page 62: ...low After satisfying these conditions setting of the QuickConnectTM compliant EtherNet IP module master must be performed according to the specified procedure Refer to the manual for the EtherNet IP module master for the procedure 1 Communication setting Disable the auto negotiation of the ports being used set the communication speed to 100 Mbps and the communication method to full duplex Change t...

Page 63: ... Attribute Value QuickConnect TM setting 0 disabled default setting 0xF5 0x01 0X0C 1 enabled QuickConnectTM response time The QuickConnectTM response time of the EX600 varies depending upon the number of I O units connected Please refer to the table below Time between power ON and I O start typical Number of I O units 1 2 3 4 5 6 7 8 9 Response time msec 370 380 390 410 430 450 480 500 520 ...

Page 64: ...of the power supply for the input output device has been detected 7Bh System Diagnosis 2 BYTE 0 No error 1 Error Bit0 The power supply voltage for output device is outside of the specification Bit1 The power supply voltage for control and input is outside of the specification Bit2 Reserved Bit3 There is a connection failure between each unit During operation Bit4 There is a connection failure betw...

Page 65: ...ut has been detected Bit7 The short circuit of the power supply for the input output device has been detected 6Eh Channel diagnosis Ch0 to Ch7 BYTE 0 No error 1 Error Bit0 There is an error in channel 0 Bit7 There is an error in channel 7 6Fh Channel diagnosis Ch8 to Ch15 BYTE 0 No error 1 Error Bit0 There is an error in channel 8 Bit7 There is an error in channel 15 70h Channel diagnosis Ch16 to ...

Page 66: ...ue input value has fallen below the set range Bit3 The analogue input value has exceeded the set range Bit4 The ON OFF counter has exceeded the set value Bit5 The open circuit has been detected Bit6 The short circuit of the valve output or digital output has been detected Bit7 The short circuit of the power supply for the input output device has been detected 1 The instance number 01h to 0Ah is al...

Page 67: ...t I O BOOL 0 Disable 1 Enable 69h Restart after output load short circuit SI Digital output I O BOOL 0 Manual 1 Auto 6Ah Input filtering time Digital input I O USINT 0 0 1 ms 1 1 0 ms 2 10 ms 3 20 ms 6Bh Input extension time Digital input I O USINT 0 1 0 ms 1 15 ms 2 100 ms 3 200 ms 6Ch Analogue data format Analogue input output I O USINT 0 Offset binary 1 Sign and Magnitude 2 2 s complement 3 Sca...

Page 68: ... value upper limit detection Analogue input output I O BOOL 0 Disable 1 Enable 7Dh Analogue user setting value of upper limit Analogue input output I O UINT 2 bytes AD value Refer to Parameter Setting for details 7Eh Analogue user setting value lower limit detection Analogue input output I O BOOL 0 Disable 1 Enable 7Fh 01h to 0Ah 1 64h to 83h 2 Get Set Analogue user setting value of lower limit An...

Page 69: ...1 Enable Clear or Force ON 87h Output setting value at communication idling Digital SI Digital output I O BOOL 0 Off Clear 1 On Force ON 88h Output setting value at communication idling Analogue Analogue output I O UINT 2 bytes AD value Refer to Parameter Setting for details 89h Analogue average filter Analogue input I O USINT 0 None 1 2 value average 2 4 value average 3 8 value average 8Ah 01h to...

Page 70: ... setting Available Not available Force I O setting Available Not available Connecting to a EX600 SEN5 X22 Ex Windows XP 1 Open a web browser on the PC 2 Type the IP address of EX600 SEN5 X22 Ex http 192 168 0 3 3 The EX600 webpage should load after several seconds Note This software operates correctly using Internet Explorer 9 If the functions do not operate correctly with Internet Explorer 10 or ...

Page 71: ...e to change the parameters only in Admin mode If the log in button is selected after the username and password are entered the display changes to Admin mode When using only the monitor function select the monitor only button Entry of the username and password is not necessary Factory default setting User name admin Password admin ...

Page 72: ... 71 EX OMR1012 5 When the Login or Monitor only button is selected the following screen will be displayed ...

Page 73: ... No 3 No 4 No 5 No 6 No 7 No 8 No 9 End plate AXA AYA DM F DX D DX C DX E DY F DY E DY B SEN Note This is an example of the display when the unit is connected as mentioned above Total I O size is displayed Select here to change the Username Password and clear Error Log When a Unit Name is selected the I O Monitor screen will be displayed page 74 Select here to log out ...

Page 74: ...the error of each unit occurs diagnostic information is displayed on the SYSTEM CONFIGURATION STATUS screen Indicates which unit the diagnostics was generated for The diagnostic log data previously generated is displayed ...

Page 75: ... 74 EX OMR1012 7 When the Unit Name is selected on the SYSTEM CONFIGURATION STATUS screen the I O monitor screen will be displayed Ex EX600 DX D Fig I O MONITOR ...

Page 76: ... 75 EX OMR1012 I O monitor screen indicates which channel generated the error Indicates which channel the diagnostics was generated for ...

Page 77: ... OMR1012 8 When the UNIT PARAMETER tab is selected the UNIT PARAMETER screen will be displayed Ex EX600 DX D When the SET button is selected after the set value has been changed the parameter will be changed ...

Page 78: ...PARAMETER screen will be displayed Ex EX600 DX D Clear method of ON OFF Counter Input 0 to the column of ON OFF Counter Clear Please push the SET button The Counter becomes 0 When the SET button is selected after the set value has been changed the parameter will be changed ...

Page 79: ...CE MODE tab is selected the following screen will be displayed Ex EX600 DX B 11 When YES button is selected the FORCE MODE screen will be displayed Ex EX600 DX B Note Please do not select the button to log out Malfunction can result ...

Page 80: ... M4 x 6 2 pcs Round head screw M3 x 8 4 pcs 2 End plate bracket EX600 ZMA2 Enclosed parts Round head screw M4 x 20 1 pc P tight screw 4 x 14 2 pcs EX600 ZMA3 Specified for SY series Enclosed parts Round head screw M4x20 with washer 1 pc P tight screw 4 x 14 2 pcs 3 Intermediate support bracket EX600 ZMB1 For direct mounting Enclosed parts Round head screw M4 x 5 2 pcs EX600 ZMB2 For DIN rail mount...

Page 81: ...M12 connector B code Socket Straight 2 m SPEEDCON compatible PCA 1564930 Cable with M12 connector B code Socket Straight 6 m SPEEDCON compatible PCA 1564943 Cable with M12 connector B code Socket Right angle 2 m SPEEDCON compatible PCA 1564969 Cable with M12 connector B code Socket Right angle 6 m SPEEDCON compatible 8 EtherNet IPTM communication cable PCA 1446566 Cable with M12 connector D code P...

Page 82: ...o change without prior notice and any obligation on the part of the manufacturer EtherNet IP is a trademark of ODVA The descriptions of products shown in this document may be used by the other companies as their trademarks 2014 SMC Corporation All Rights Reserved ...