-15-
No.EX##-OMK0004-A
LED Indication and Settings
○
LED indication
Display
Contents
OFF
Insufficient power supply for solenoids
SOL
Green light ON
Normal power supply for solenoids
OFF
Insufficient power supply for input and control
PWR
Green light ON
Normal power supply for input and control
OFF
The power supply for control is OFF
Green light ON
Operating normally
Green flashes
Setting error (Device has not been configured)
Red light ON
Unrecoverable internal error
MS
Red flashes
Recoverable internal error
OFF
The power supply for control is OFF or IP address not set
Green light ON
EtherNet/IP
TM
-level communication not established
Green flashes
Multiple EtherNet/IP
TM
-level communications established
Red light ON
IP address duplicated
NS
Red flashes
Multiple EtherNet/IP
TM
-level communications time out