1. Check the specifications.

Read the specifications carefully and use this product 
appropriately. The product may be damaged or malfunction if it 
is used outside the range of specifications of current current, 
voltage, temperature or impact.

2. Use caution when multiple cylinders are used 

and close to each other.

When two or more auto switch cylinders are lined up in close 
proximity to each other, magnetic field interference may cause 
the switches to malfunction. Maintain a minimum cylinder 
separation of 40 mm. (When the allowable interval is specified 
for each cylinder series, use the indicated value.) 

3. Use caution to the ON time of a switch at the 

intermediate position of stroke.

When an auto switch is placed at an intermediate position of 
the stroke and a load is driven at the time the piston passes, 
the auto switch will operate, but if the speed is too great, the 
operating time will be shortened and the load may not operate 
properly. The maximum detectable piston speed is:

In cases of high piston speed, the use of an auto switch (D-
F5NT/F7NT/G5NT and M5

T) with a built-in OFF delay timer 

(

 200 ms) makes it possible to extend the load operating time.

4. Wiring should be kept as short as possible.

<Reed switches>
As the length of the wiring to a load gets longer, the rush 
current at switching ON becomes greater, and this may 
shorten the product’s life. (The switch will stay ON all the time.)
1) For an auto switch without a connect protection circuit, use 

a contact protection box when the wire length is 5 m or 
longer.

2) Even if an auto switch has a built-in contact protection 

circuit, when the wiring is more than 30 m long, it is not able 
to adequately absorb the rush current and its life may be 
reduced. It is again necessary to connect a contact 
protection box in order to extend its life. Please contact 
SMC in this case.

<Solid state switches>
3) Although wire length should not affect switch function, use a 

wire 100 m or shorter.

5. Use caution to the internal voltage drop of a 

switch.

<Reed switches>
1) Switches with an indicator light (Except D-A56/A76H/A96/ 

A96V/C76/E76A/Z76)

• If auto switches are connected in series as shown below, 

take note that there will be a large voltage drop because of 
internal resistance in the light emitting diodes. (Refer to 
internal voltage drop in the auto switch specifications.)
[The voltage drop will be “n” times larger when “n” auto 
switches are connected.]
Even though an auto switch operates normally, the load 
may not operate.

• Similarly, when operating below a specified voltage, it is 

possible that the load may be ineffective even though the 
auto switch function is normal. Therefore, the formula below 
should be satisfied after confirming the minimum operating 
voltage of the load.

 

2) If the internal resistance of a light emitting diode causes a 

problem, select a switch without an indicator for right 
(MODEL D-A6

/A80/A80H/A90/A90V/C80/R80/90/E80A/ 

Z80)

<Solid state switches>
3) Generally, the internal voltage drop will be greater with a 2- 

wire solid state auto switch than with a reed switch. Take 
the same precautions as in 1).
Also note that a 12 VDC relay is not applicable.

6. Use caution to the leakage current.

<Solid state switches>
With a 2-wire solid state auto switch, current (leakage current) 
flows to the load to operate the internal circuit even when in 
the OFF state.

 
If the condition given in the above formula is not met, it will not 
reset correctly (stays ON). Use a 3-wire switch if this 
specification cannot be satisfied.
Moreover, leakage current flow to the load will be “n” times 
larger when “n” auto switches are connected in parallel.

7. Do not use a load that generates surge voltage.

<Reed switches>
If driving a load such as a relay that generates a surge 
voltage, use a switch with a built-in contact protection circuit or 
use a contact protection box.
<Solid state switches>
Although a zener diode for surge protection is connected at 
the output side of a solid state auto switch, damage may still 
occur if the surge is applied repeatedly. When a load, such as 
a relay or solenoid, which generates surge is directly driven, 
use a type of switch with a built-in surge absorbing element.

8. Cautions for use in an interlock circuit

When an auto switch is used for an interlock signal requiring 
high reliability, devise a double interlock system to avoid 
trouble by providing a mechanical protection function, or by 
also using another switch (sensor) together with the auto 
switch.
Also perform periodic maintenance inspections and confirm 
proper operation.

9. Ensure sufficient space for maintenance 

activities.

When designing an application, be sure to allow sufficient 
space for maintenance and inspection.

Design and Selection

V (mm/s) = 

Auto switch operating range (mm)

Load operating time (ms)

 x 1000

Load

Supply  
voltage 

 

Internal voltage
 drop of switch

 

>

 

Minimum operating
 voltage of load    

Current to operate load (OFF condition) > Leakage current

Warning

Auto Switches

Precautions 1

Be sure to read before handling. 
For detailed precautions on every series, refer to main text.

12-13-2

1st

12_13_D-.qxd  04.7.6 18:01  Page 13-2

2

Summary of Contents for D-M9B

Page 1: ...9B D M9NV M9PV M9BV D Y59A Y7P Y59B D Y69A Y7PV Y69B D Y7NW Y7PW Y7BW D Y7NWV Y7PWV Y7BWV D F9NW F9PW F9BW D F9NWV F9PWV F9BWV Grommet Grommet Grommet Grommet Grommet Grommet Grommet Grommet Grommet Grommet Grommet Grommet Grommet Note As for the applicable auto switches on Rotary Actuators refer to pages in Best Pneumatics Vol 11 Connector Connector Connector Connector Tie rod Tie rod Tie rod Tie...

Page 2: ...ates normally the load may not operate Similarly when operating below a specified voltage it is possible that the load may be ineffective even though the auto switch function is normal Therefore the formula below should be satisfied after confirming the minimum operating voltage of the load 2 If the internal resistance of a light emitting diode causes a problem select a switch without an indicator...

Page 3: ...or changes Lead wire colors of SMC auto switches have been changed in order to meet NECA Standard 0402 for production beginning September 1996 and thereafter Please refer to the tables provided 2 wire 3 wire Solid State with Diagnostic Output Solid State with Latch Type Diagnostic Output Output Output Power supply Power supply GND Output Diagnostic output Power supply Power supply GND Output Power...

Page 4: ... with SMC regarding the need to use a solid state switch depending on the environment 7 Do not use in locations where surges are generated Solid state switches When there are units solenoid type lifters high frequency induction furnaces motors etc which generate a large amount of surge in the area around cylinders with solid state auto switches this may cause deterioration or damage to the switche...

Page 5: ...tion box should be used in any of the above conditions Unless using a contact protection box the contact life may be shortened Due to permanent energizing conditions D A72 H must be used with the contact protection box regardless of load styles and lead wire length 2 Please contact SMC when using built in contact protection circuit style D A34 A C D A44 A C D A54 A64 D B54 B64 D A59W D B59W in the...

Page 6: ... Switch 2 Black Blue Relay Relay Brown Black Blue Load Relay contact Switch 1 Switch 2 Brown Blue Brown Blue Load Switch 1 Switch 2 Brown Blue Brown Blue Load AND connection for NPN output Using relays 2 wire Switch 1 Brown Switch 2 Black Blue Load Brown Black Blue AND connection for NPN output Performed with switches only The indicator lights will light up when both switches are turned ON When tw...

Page 7: ...of the above listed situations The contact point life may decrease Refer to page 12 13 5 for contact protection box LED Reed switch Resistor Zener diode Brown Blue Reed switch Blue LED Reed switch Resistor Zener diode Brown Choke coil Contact protection box CD P11 Surge absorber 앑 3 Lead wire Oil resistant vinyl heavy duty cord ø3 4 0 2 mm2 2 cores Brown Blue 0 5 m Note 1 Regarding the common spec...

Page 8: ... Load DC power supply Blue LED Reed switch Resistor Zener diode Brown OUT Blue OUT Brown Choke coil Contact protection box CD P11 Surge absorber 앑 Reed switch OUT Brown 앑 Note 1 Operating load is an induction load Note 2 In the case the wiring length to load is more than 5 m Note 3 Wiring to the load is 5 m or longer Use the contact protection box in any of the above listed situations The contact ...

Page 9: ...d switch Resistor Zener diode Brown OUT Blue OUT Brown Choke coil Contact protection box CD P12 Zener diode Reed switch Contact protection box CD P11 CD P12 OUT Brown 앑 OUT Blue Connector Note 1 Operating load is an induction load Note 2 Wiring to the load is 5 m or longer Use the contact protection box in any of the above listed situations The contact point life may decrease Refer to page 12 13 5...

Page 10: ...0 D A93 6 30 D A93V 6 30 D A96 8 41 D A96V 8 41 g Weight Auto Switch Internal Circuit Colors of lead wire inside are the ones before conformed to IEC standard D A90V D A93V D A96V Reed switch OUT Brown 앑 OUT Blue Blue Black LED Reed switch Resistor Zener diode Brown Red OUT Brown 앑 OUT Blue LED Reed switch Resistor Reverse current prevention diode OUT Black DC Brown DC Blue Load DC power supply Di...

Page 11: ...own Blue 0 5 m Note 1 Regarding the common specifications of the reed switches refer to page 12 13 5 Note 2 Regarding the lead wire length refer to page 12 13 5 Note 3 Under 5 mA the strength of the indicator light is poor In some cases visibility of the indicator light will not be possible where the output signal is less than 2 5 mA However there is no problem in terms of contact output when an o...

Page 12: ...or less 100 µA or less at 24 VDC D J79 2 wire 24 VDC Relay PLC 24 VDC 10 to 28 VDC 5 to 40 mA 4 V or less 0 8 mA or less at 24 VDC 13 57 92 11 50 81 13 57 92 Lead wire Oil resistant vinyl heavy duty cord ø3 4 0 2 mm2 3 cores Brown Black Blue 2 cores Brown Blue 0 5 m Note 1 Regarding the common specifications of the solid state switches refer to page 12 13 5 Note 2 Regarding the lead wire length re...

Page 13: ...or less at 24 VDC 3 wire IC circuit Relay PLC 5 12 24 VDC 4 5 to 28 VDC 10 mA or less 100 µA or less at 24 VDC Lead wire Oil resistant vinyl heavy duty cord ø3 4 0 2 mm2 3 cores Brown Black Blue 2 cores Brown Blue 0 5 m Note 1 Regarding the common specifications of the solid state switches refer to page 12 13 5 Note 2 Regarding the lead wire length refer to page 12 13 5 Auto Switch Specifications ...

Page 14: ...pecifications of the solid state switches refer to page 12 13 5 Note 2 Regarding the lead wire length refer to page 12 13 5 Auto Switch Specifications PLC Abbreviation of Programmable Logic Controller Weight g Dimensions 1 Confirm that the connector is appropriately tightened If tightened insufficiently the waterproof performance will deteriorate 2 Refer to Best Pneumatics Vol 6 7 8 9 10 for the d...

Page 15: ...del 0 5 3 5 D F8N 7 32 52 D F8P 7 32 52 D F8B 7 32 52 Lead wire length m Lead wire Oil resistant vinyl heavy duty cord ø2 7 0 5 m D F8N D F8P 0 15 mm2 x 3 cores Brown Black Blue D F8B 0 18 mm2 x 2 cores Brown Blue Note 1 Regarding the common specifications of the solid state switches refer to page 12 13 5 Note 2 Regarding the lead wire length refer to page 12 13 5 Fix the switch with appropriate s...

Page 16: ... this product series When it is wired incorrectly or a load is short circuited a switch may be damaged or burned In the event of stripping cable sheath use caution for the stripping direction Its insulation may be torn or damaged depending on the direction Below is given as the recommended tool As for 2 wire a stripper for round shape cord ø2 0 is usable Fix the switch with appropriate screw insta...

Page 17: ...e 0 5 m Note 1 Regarding the common specifications of the solid state switches refer to page 12 13 5 Note 2 Regarding the lead wire length refer to page 12 13 5 Weight g Dimensions Auto switch model 0 5 3 5 D Y59B D Y69B 9 50 83 D Y59A D Y69A 10 53 87 D Y7P V 10 53 87 Lead wire length m A B A B Auto Switch Internal Circuit D Y59A D Y69A D Y59B D Y69B D Y7P D Y7PV D Y59A D Y7P D Y59B D Y69A D Y7PV ...

Page 18: ... load current Lead wire Oil resistant vinyl heavy duty cord ø3 4 0 2 mm2 3 cores Brown Black Blue 2 cores Brown Blue 0 5 m Note 1 Regarding the common specifications of the solid state switches refer to page 12 13 5 Note 2 Regarding the lead wire length refer to page 12 13 5 The optimum operating position can be determined by the color of the light Red Green Red Auto Switch Specifications PLC Abbr...

Page 19: ...M2 5 x 4l Slotted set screw Indicator light Most sensitive position Mounting screw M2 5 x 4l Slotted set screw Indicator light SMC SMC 6 2 5 2 5 29 ø3 4 12 5 27 3 6 2 5 12 5 8 5 2 5 ø3 4 Most sensitive position Auto Switch Specifications PLC Abbreviation of Programmable Logic Controller Lead wire Oil resistant flexible vinyl heavy duty cord ø3 4 0 15 mm2 3 cores Brown Black Blue 2 cores Brown Blue...

Page 20: ...itive position 6 Mounting screw M2 5 x 4l Slotted set screw Indicator light 4 3 2 3 8 3 1 6 2 4 ø2 7 Most sensitive position 6 4 6 2 8 20 D F9 WV D F9 W Indicator light Display method Auto switch model 0 5 3 5 D F9NW V 7 34 56 D F9PW V 7 34 56 D F9BW V 7 32 52 Lead wire length m Auto Switch Specifications PLC Abbreviation of Programmable Logic Controller Lead wire Oil resistant vinyl heavy duty co...

Page 21: ...al operation IC circuit Relay PLC 5 12 24 VDC 4 5 to 28 VDC 10 mA or less 28 VDC or less 50 mA or less at the total amount of normal output and diagnostic output 1 5 V or less 0 8 V or less at 5 mA 100 µA or less at 24 VDC Operating position Red LED lights when ON Optimum operating position Green LED lights when ON Lead wire Oil resistant vinyl heavy duty cord ø3 4 0 2 mm2 4 cores Brown Black Oran...

Page 22: ...uto switch model 0 5 3 5 D F7BA 50 81 D F7BAV 50 81 Lead wire length m In line Lead wire Oil resistant vinyl heavy duty cord ø3 4 0 2 mm2 2 cores Brown Blue 3 m Standard Note 1 Regarding the common specifications of the solid state switches refer to page 12 13 5 Note 2 Regarding the lead wire length refer to page 12 13 5 Auto Switch Specifications PLC Abbreviation of Programmable Logic Controller ...

Page 23: ... 5 m Note 1 Regarding the common specifications of the solid state switches refer to page 12 13 5 Note 2 Regarding the lead wire length refer to page 12 13 5 D F9BAL With indicator light Auto switch model Auto switch model 0 5 3 5 Lead wire length m D F9BA 37 57 Auto Switch Specifications PLC Abbreviation of Programmable Logic Controller Weight g M2 5 x 4l Slotted set screw Indicator light Most se...

Page 24: ... ON Lead wire Oil resistant flexible vinyl heavy duty cord ø3 4 0 15 mm2 2 cores Brown Blue 3 m Standard Note 1 Regarding the common specifications of the solid state switches refer to page 12 13 5 Note 2 Regarding the lead wire length refer to page 12 13 5 Auto Switch Specifications PLC Abbreviation of Programmable Logic Controller Weight g Precautions Operating range Indication Green Red Red Opt...

Page 25: ... Grommet Perpendicular Grommet Perpendicular Applicable model F79 F7P J79 F7NV F7PV F7BV F79W F7PW J79W F7NWV F7BWV F79F F7BA F7NT P5DW H7A1 H7A2 H7B Electrical entry G59 G5P K59 H7NW H7PW H7BW G59W G5PW K59W H7NF G59F H7BA G5BA G5NT F59 F5P J59 F59W F5PW J59W F59F F5BA F5NT Wide detection 앬 앬 G5NB Function 0 5 Lead wire length 1 0 3 0 Mounting 2 color indication Direct mounting style Rotary actua...

Page 26: ...r 3 4 Number of pins Applicable series example Connector model M8 3 pin 4 pin M12 4 pin As the parts are not supplied from SMC refer to the application examples listed in the below For detail such as catalog availability etc please contact each manufacturer ø14 44 Sensor section ø10 31 4 Sensor section Connector Specifications Connector model M8 3 pin M8 4 pin M12 4 pin JIS C 4524 JIS C 4525 IEC 9...

Page 27: ...no All the solid state switches with the exceptance of D J51 output diagnostic type terminal conduit type connector type magnetic field resistant type heat resistant type Note A B A B Oil resistant flexible cabtire cord is used for D Y59 Y69 Y7P V as standard No need to suffix 61 to the end of part number Specifications are the same as standard products with the exception of lead wire specificatio...

Reviews: