Piping

 

 

 

AXTS040*-2(B)-X2 

Symbol for internal pilot fluid passage 

 

       

Fig.3    Symbol for internal pilot fluid passage. 

 

 
Caution 

 

 

Continuous blow air can be changed to pulse air without electrical wiring by connecting the 
pulse blow valve between air blow 2 port valve and nozzle of existing equipment.

 

 

When an air gun and a pressure regulator are connected to OUT port, the back pressure of 
the OUT port will be high.

 

Therefore, the product cannot be used.

 

 

When  a  vacuum  ejector  and  a  suction  filter  are  connected  to  the  OUT  port,  the  back 
pressure of the OUT port will be higher due to the clogging of the filter and silencer of the 
vacuum  ejector  during  operation.  Therefore,  the  product  cannot  be  used.  In  that  case, 
please use the external pilot type to avoid the influence of the back pressure.

 

 

Keep using the plug and port with silencer. 

 

Direct manual override is operated by flat blade screwdriver. Insert the flat blade driver to 
the groove until it contacts the bottom of the groove and turn the driver 90 
degrees.   Rotating direction does not matter. Do the same for release (push and rotate for 
90 degrees). 

 

Tighten the piping using the correct torque shown below. 
 
Table.1 

Thread 

Appropriate tightening 

torque (Nm) 

1/2 

20 to 25 

 

AXTS040*-2(B)-X2 

Air blow 
2-port valve 

OUT Port 
4(A) 

IN 

Summary of Contents for AXTS040 2 X2 Series

Page 1: ...1 Product name Pulse Blow Valve Model Series Product Number AXTS040 2 3 B X2 Doc No AXTS OMY0007 A Operation Manual SMC Corporation...

Page 2: ...4 1 Specifications P 5 2 Port size and P 5 flow characteristics 3 How to Order P 5 4 Configuration symbol P 6 5 Piping method P 7 8 6 Frequency adjustment P 9 10 7 Mounting P 11 8 Environment P 11 9 L...

Page 3: ...e when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly The assembly oper...

Page 4: ...distance or replacement parts Please consult your nearest sales branch For any failure or damage reported within the warranty period which is clearly our responsibility a replacement product or necess...

Page 5: ...oof pressure 1 5MPa Ambient and fluid temperature 20 to 60 o C Lubrication No Enclosure rating IP65 equivalent Weight About 1 400g Use an External pilot pressure higher than IN port pressure 2 Port si...

Page 6: ...r for air blow 4 A Port OUT Port 3 R2 Port Released to atmosphere pilot exhaust port with silencer AXTS040 3 B X2 Symbol for internal pilot fluid passage Fig 2 Symbol for external pilot fluid passage...

Page 7: ...ure of the OUT port will be higher due to the clogging of the filter and silencer of the vacuum ejector during operation Therefore the product cannot be used In that case please use the external pilot...

Page 8: ...minimum operating pressure the same air can be connected to the IN port and X port Refer to Fig 5 When the product is used in a condition where the OUT port back pressure varies for example vacuum eje...

Page 9: ...ne needle is adjusted the time for the opposite side will be slightly changed Internal pilot 1 to 5HZ and external pilot 1 to 8Hz is reference The charts on page 10 show the relation for the adjustmen...

Page 10: ...6 8 Hz ON 7 5 3 1 OFF AXTS040 3 B X2 ON 1 3 5 7 0 1 Hz 0 1 Hz 0 1 Hz 0 1 Hz 2 2 1 1 2 0 Hz 2 3 Hz 2 4 Hz 2 0 Hz 29 17 15 14 3 7 Hz 4 8 Hz 4 9 Hz 4 8 Hz 51 36 32 24 4 3 Hz 6 0 Hz 6 4 Hz 6 7 Hz 58 43 4...

Page 11: ...pool and sleeve which may cause the spool to stick In this situation the type of the compressor lubricating oil should be replaced with a good quality compressor lubrication oil that generates less ox...

Page 12: ...12 Revision history A Modify items in graph This manual is subject to change without prior notice 2020 SMC Corporation All Rights Reserved https www smcworld com...

Reviews: