2.
Adjust pump compensator:
a. Loosen and remove flow control cap. Reference Figure 34.
b. Loosen the flow control pressure jam nut.
c.
While monitoring the generator’s output voltage, slowly rotate the flow control set
screw with a 3mm hex
wrench. Adjust the flow control until the generator’s output
frequency is 64-65 Hz for 60 Hz application, or 54-55 Hz for 50 Hz application.
d. While keeping the setscrew from rotating, with the hex wrench, re-tighten the jam
nut.
e. Replace and tighten the flow control cap.
Figure 34
– Pump Assembly