HGM9520N Genset Paralleled Controller User Manual Page 76 of 111
No.
Items
Parameters
Defaults
Description
Voltage
(0~200.0)%
(0~20.0)s
90.0
0.1
8.
Mains
Over
Frequency
(0~1)
(0~200.0)%
(0~20.0)s
1
101.0
0.1
Set value is mains rated frequency’s
percentage.
9.
Mains
Under
Frequency
(0~1)
(0~200.0)%
(0~20.0)s
1
99.0
0.1
10.
ROCOF
(0~1)
(0~1.00)Hz/s
(0~20.0)s
1
0.20
0.1
Set value is frequency change rate of mains
(ROCOF).
11.
Vector Shift
(0~1)
(0~20.0)
°
(0~20.0)s
1
6.0
0.1
Set value is phase angle’s change rate of
mains voltage waveform (VECTOR SHIFT).
Expansion Module
1.
Expand DIN16
(0~1)
0
0: Disable ; 1: Enable
2.
Expand DOUT16
(0~1)
0
0: Disable ; 1: Enable
3.
Expand AIN24 1
(0~1)
0
0: Disable ; 1: Enable
4.
Expand AIN24 2
(0~1)
0
0: Disable ; 1: Enable
5.
Expand AIN8
(0~1)
0
0: Disable ; 1: Enable