HGM9520N Genset Paralleled Controller User Manual Page 60 of 111
No.
Items
Parameters
Defaults
Description
(0~3600)s
(0~7)
3
7
Delay value
Action
10.
Under Speed 2 Set
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
1
86.0
90.0
5
1
0: Disable 1: Enable
Setting value is rated speed percentage.
Return value is rated speed percentage.
Delay value
Action
11.
Battery
Rated
Voltage
(0~60.0)V
24.0
Standard for detecting of over/under
voltage of battery.
12.
Battery Over Volt 1
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
1
120.0
115.0
60
1
0: Disable 1: Enable
Set value is batt. rated volt percentage.
Return value is batt. rated volt percentage.
Delay value
Action
13.
Battery Over Volt 2
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
0
120.0
115.0
60
0
0: Disable 1: Enable
Set value is batt. rated volt percentage.
Return value is batt. rated volt percentage.
Delay value
Action
14.
Battery Under Volt
1
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
1
85.0
90.0
60
1
0: Disable 1: Enable
Set value is batt. rated volt percentage.
Return value is batt. rated volt percentage.
Delay value
Action
15.
Battery Under Volt
2
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
0
85.0
90.0
60
0
0: Disable 1: Enable
Set value is batt. rated volt percentage.
Return value is batt. rated volt percentage.
Delay value
Action
16.
Charge Alt Fail
(0~1)
(0~60.0)V
(0~60.0)V
(0~3600)s
(0~7)
1
8.0
10.0
10
1
0: Disable 1: Enable
Setting value
Return value
Delay value
Action
17.
Start Attempts
(1~10) times
3
Maximum crank times for start failures;
when it reaches this, controller will send
start failure signal.
18.
Crank Disconnect
(0~6)
2
There are 3 conditions of disconnecting
starter with engine. Each condition can be
used alone and simultaneously to separate
the start motor and engine as soon as
possible.
19.
Disconnect
(0~200.0)%
24.0
Percentage of the generating rated