Smartgen HGM7100N Series User Manual Download Page 9

                                             

HGM7100N GENSET CONTROLLER USER MANUAL 

HGM7100N Genset Controller                        2017-08-26                      Version1.0                Page 22 of 48 

SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS 

8.1  CONTENTS AND SCOPES OF PARAMETERS   

Table 10 - Parameters Settings and Scope 

No. 

Items 

Range 

Default 

Description 

Mains 

AC System 

(0-3) 

0: 3P4W; 
1: 3P3W 

2: 2P3W 

3: 1P2W 

Mains 

Rated 

Voltage 

(30-30000)V 

230 

Provide  standard  for  judging  whether  mains 
over/under  voltage  or  not;  if  used  voltage 
transformer,  this  value  is  primary  voltage  of 
transformer.     

Mains 

Rated 

Frequency 

(10.0-75.0)Hz 

50.0 

Provide  standard  for  judging  whether  mains 
over/under frequency or not. 

Mains 

Normal 

Delay 

(0-3600)s 

10 

The time from mains abnormal to normal. 

Mains 

Abnormal 

Time 

(0-3600)s 

The time from mains normal to abnormal. 

Mains 

Voltage 

Transformer (PT) 

(0-1) 

0: Disabled; 1: Enabled 

Mains Over Voltage  (0-200)% 

120 

The  setting  value  is  mains  rated  voltage 
percentage; return value and delay value also 
can be set. 

Mains 

Under 

Voltage 

(0-200)% 

80 

Mains 

Over 

Frequency   

(0-200)% 

Disabled  The  setting  value  is  mains  rated  frequency 

percentage; return value and delay value also 
can be set. 

10 

Mains 

Under 

Frequency 

(0-200)% 

Disabled 

11 

Mains 

Loss 

of 

Phase Check 

(0-1) 

0: Disabled; 1: Enabled 

12 

Mains 

Reverse 

Phase   

(0-1) 

Timers 

Start Delay 

(0-3600)s 

Time  from  mains  abnormal  or  remote  start 
signal is active to start gen-set. 

Return Delay 

(0-3600)s 

Time  from  mains  normal  or  remote  start 
signal is deactivated to genset stop. 

Preheat Delay 

(0-3600)s 

Power-on time of heater plug before starter is 
powered up. 

Cranking Time 

(3-60)s 

Each starter power-on time. 

Crank Rest Time 

(3-60)s 

10 

The  waiting  time  before  second  power  up 
when engine starts fail. 

Safety On Time 

(0-3600)s 

10 

Alarms for low oil pressure, high temp, under 
speed,  under  frequency/voltage,  charge  alt 
failure are deactivated. 

Start Idle Time 

(0-3600)s 

Idle speed running time when gen-set start up. 

Summary of Contents for HGM7100N Series

Page 1: ...HGM7100N SERIES HGM7110N 7120N GENSET CONTROLLER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD...

Page 2: ...13 5 2 1 MANUAL SWITCHING PROCESS 13 5 2 2 AUTO SWITCHING PROCESS 13 6 PROTECTION 14 6 1 WARNINGS 14 6 2 SHUTDOWN ALARM 16 6 3 TRIP AND STOP ALARM 18 6 4 TRIP ALARM 18 7 WIRINGS CONNECTION 19 8 SCOPES...

Page 3: ...SER MANUAL HGM7100N Genset Controller 2017 08 26 Version1 0 Page 4 of 48 11 SENSOR SETTING 42 12 COMMISSIONING 43 13 TYPICAL APPLICATION 44 14 INSTALLATION 46 14 1 FIXING CLIPS 46 14 2 OVERALL DIMENSI...

Page 4: ...r close or open in C O interface under manual mode only suit for HGM7120N Close Pressing this key to control breaker close under user manual mode only suit for HGM7110N Open Pressing this key to contr...

Page 5: ...t Panel Indication Figure 2 HGM7120N Front Panel Indication NOTE Part of indicator lights illustration Table 4 Alarm Indicator Description Alarm Type Alarm Indicators Warning alarm slowly flash once p...

Page 6: ...ted with negative of starter battery 2 B 2 5mm2 Connected with positive of starter battery If wire length is over 30m better to double wires in parallel Max 20A fuse is recommended 3 Emergency Stop 2...

Page 7: ...to see table 12 23 Aux Input 2 1 0mm2 Ground connected is active B 24 Aux Input 3 1 0mm2 Ground connected is active B 25 Aux Input 4 1 0mm2 Ground connected is active B 26 Aux Input 5 1 0mm2 Ground c...

Page 8: ...t 1 0mm2 Connected to S phase of mains 2A fuse recommended HGM7110N without 42 Mains T phase voltage monitoring input 1 0mm2 Connected to T phase of mains 2A fuse recommended HGM7110N without 43 Mains...

Page 9: ...The setting value is mains rated voltage percentage return value and delay value also can be set 8 Mains Under Voltage 0 200 80 9 Mains Over Frequency 0 200 Disabled The setting value is mains rated...

Page 10: ...conditions and inspecting engine speed Details to see the following installation description 3 Engine Rated Speed 0 6000 RPM 1500 Provide standard for judging over under speed and on load speed 4 Spe...

Page 11: ...higher than the setting value starter will disconnect Details to see the following installation description 19 Oil Pressure of Crank Disconnect 0 1000 kPa 200 When engine oil pressure is higher than t...

Page 12: ...ge Shutdown 0 200 80 10 Gen Over Frequency Shutdown 0 200 114 The setting values are rated frequency percentage of generator and delay value can be set 11 Gen Under Frequency Shutdown 0 200 80 12 Gen...

Page 13: ...de 0 2 0 0 Stop Mode 1 Manual Mode 2 Auto Mode 2 Communication Address 1 254 1 Controller address while in remote monitoring status 3 Communication Stop bit Setting 0 1 1 0 2 bit stop bit 1 1 bit stop...

Page 14: ...nected oil pressure sensor is lower than the setting point controller will initiate low oil pressure warning alarm judgment only starts after safety on delay expired Return value and delay value can b...

Page 15: ...panel are inactive except for and displays on the right side of the first line of LCD status page 7 Reserved 8 Idle Control Mode Under speed under frequency and under voltage are not protected in thi...

Page 16: ...HGM7100N GENSET CONTROLLER USER MANUAL HGM7100N Genset Controller 2017 08 26 Version1 0 Page 44 of 48 13 TYPICAL APPLICATION Figure 5 HGM7100N Typical Application Figure 6 HGM7120N Typical Application...

Page 17: ...ANUAL HGM7100N Genset Controller 2017 08 26 Version1 0 Page 45 of 48 Figure 7 Single Phase 2 Wire Connection Diagram Figure 8 2Phase 3Wire Connection Diagram NOTE Expand relay with high capacity in st...

Page 18: ...and negative input ports in order to prevent charge disturbing the controller s normal working a SPEED SENSOR INPUT Speed sensor is the magnetic equipment which be installed in starter and for detecti...

Reviews: