HGM7100N GENSET CONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 20 of 48
No.
Function
Cable Size
Remarks
9
Normally
open
output,
rated 8A.
10
Aux. Output 3(16A 250VAC)
2.5 mm
2
Relay normally open volt
free contact, rated 16A,
volt free contact output.
11
12
Aux. Output 4(16A 250VAC)
2.5 mm
2
13
14 Charger(D+)
1.0mm
2
Connected with charger starter’s D+ (WL) terminals.
Being hang up If there is no this terminal.
15 Aux. Output 5(7A)
1.5 mm
2
B+ is supplied by No.2
terminal, rated 7A
Details see Table 11
16 Aux. Output 6(7A)
1.5 mm
2
17 Speed Sensor Input
Connect with speed sensor, shielded wire is recommended.
18
Speed sensor input, battery
negative electrode has been
connected to the inside of
controller.
19 Engine Temp.
Connected with temperature sensor
Details to see table 13
20 Oil Pressure
Connected with pressure sensor
21 Fuel Level
Connected with fuel level sensor
22 Aux. Input 1
1.0mm
2
Ground connected is active (B-)
Details to see table 12
23 Aux. Input 2
1.0mm
2
Ground connected is active (B-)
24 Aux. Input 3
1.0mm
2
Ground connected is active (B-)
25 Aux. Input 4
1.0mm
2
Ground connected is active (B-)
26 Aux. Input 5
1.0mm
2
Ground connected is active (B-)
27 Sensor Common Port
Sensor common port, battery negative electrode has been
connected to the inside of controller.
28 Aux. Input 6
1.0mm
2
Ground connected is active (B-)
Details to see table 12
29 Aux. Input 7
1.0mm
2
Ground connected is active (B-)
30 Configurable Sensor 1
Connected with temp/pressure/fuel level
sensor.
Details to see table 13
31 Configurable Sensor 2
32 CT A-phase Monitoring Input 1.5mm
2
Outside connected to secondary coil of CT (5A rated).
33 CT B-phase Monitoring Input 1.5mm
2
Outside connected to secondary coil of CT (5A rated).
34
CT
C-phase
Monitoring
Input
1.5mm
2
Outside connected to secondary coil of CT (5A rated).
35 CT Common Port
1.5mm
2
Details to see the following installation description.
36
Gen
U-phase
Voltage
Monitoring Input
1.5mm
2
Connected to U-phase output of genset (2A fuse
recommended).
37
Gen
V-phase
Voltage
Monitoring Input
1.0mm
2
Connected to V-phase output of genset (2A fuse
recommended).