HGM7100N GENSET CONTROLLER USER MANUAL 

HGM7100N Genset Controller                        2017-08-26                      Version1.0                Page 20 of 48 

No. 

Function 

Cable Size 

Remarks 

Normally 

open 

output, 

rated 8A. 

10 

Aux. Output 3(16A 250VAC) 

2.5 mm

2

 

Relay  normally  open  volt 

free  contact,  rated  16A, 

volt free contact output. 

11 

12 

Aux. Output 4(16A 250VAC) 

2.5 mm

2

 

13 

14  Charger(D+) 

1.0mm

2

 

Connected  with  charger  starter’s  D+  (WL)  terminals. 

Being hang up If there is no this terminal. 

15  Aux. Output 5(7A) 

1.5 mm

2

 

B+  is  supplied  by  No.2 

terminal, rated 7A 

Details see Table 11 

16  Aux. Output 6(7A) 

1.5 mm

2

 

17  Speed Sensor Input 

Connect with speed sensor, shielded wire is recommended.   

18 

Speed  sensor  input,  battery 

negative electrode has been 

connected  to  the  inside  of 

controller. 

19  Engine Temp. 

Connected with temperature sensor 

Details to see table 13 

20  Oil Pressure 

Connected with pressure sensor 

21  Fuel Level   

Connected with fuel level sensor 

22  Aux. Input 1 

1.0mm

2

 

Ground connected is active (B-) 

Details to see table 12 

23  Aux. Input 2 

1.0mm

2

 

Ground connected is active (B-) 

24  Aux. Input 3 

1.0mm

2

 

Ground connected is active (B-) 

25  Aux. Input 4 

1.0mm

2

 

Ground connected is active (B-) 

26  Aux. Input 5 

1.0mm

2

 

Ground connected is active (B-) 

27  Sensor Common Port 

Sensor  common  port,  battery  negative  electrode  has  been 

connected to the inside of controller. 

28  Aux. Input 6 

1.0mm

2

 

Ground connected is active (B-) 

Details to see table 12 

29  Aux. Input 7 

1.0mm

2

 

Ground connected is active (B-) 

30  Configurable Sensor 1 

Connected  with  temp/pressure/fuel  level 

sensor. 

Details to see table 13 

31  Configurable Sensor 2 

32  CT A-phase Monitoring Input  1.5mm

2

 

Outside connected to secondary coil of CT (5A rated). 

33  CT B-phase Monitoring Input  1.5mm

2

 

Outside connected to secondary coil of CT (5A rated). 

34 

CT 

C-phase 

Monitoring 

Input 

1.5mm

2

 

Outside connected to secondary coil of CT (5A rated). 

35  CT Common Port 

1.5mm

2

 

Details to see the following installation description. 

36 

Gen 

U-phase 

Voltage 

Monitoring Input 

1.5mm

2

 

Connected to U-phase output of genset (2A fuse 

recommended). 

37 

Gen 

V-phase 

Voltage 

Monitoring Input 

1.0mm

2

 

Connected to V-phase output of genset (2A fuse 

recommended). 

Summary of Contents for HGM7100N Series

Page 1: ...HGM7100N SERIES HGM7110N 7120N GENSET CONTROLLER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD...

Page 2: ...13 5 2 1 MANUAL SWITCHING PROCESS 13 5 2 2 AUTO SWITCHING PROCESS 13 6 PROTECTION 14 6 1 WARNINGS 14 6 2 SHUTDOWN ALARM 16 6 3 TRIP AND STOP ALARM 18 6 4 TRIP ALARM 18 7 WIRINGS CONNECTION 19 8 SCOPES...

Page 3: ...SER MANUAL HGM7100N Genset Controller 2017 08 26 Version1 0 Page 4 of 48 11 SENSOR SETTING 42 12 COMMISSIONING 43 13 TYPICAL APPLICATION 44 14 INSTALLATION 46 14 1 FIXING CLIPS 46 14 2 OVERALL DIMENSI...

Page 4: ...r close or open in C O interface under manual mode only suit for HGM7120N Close Pressing this key to control breaker close under user manual mode only suit for HGM7110N Open Pressing this key to contr...

Page 5: ...t Panel Indication Figure 2 HGM7120N Front Panel Indication NOTE Part of indicator lights illustration Table 4 Alarm Indicator Description Alarm Type Alarm Indicators Warning alarm slowly flash once p...

Page 6: ...ted with negative of starter battery 2 B 2 5mm2 Connected with positive of starter battery If wire length is over 30m better to double wires in parallel Max 20A fuse is recommended 3 Emergency Stop 2...

Page 7: ...to see table 12 23 Aux Input 2 1 0mm2 Ground connected is active B 24 Aux Input 3 1 0mm2 Ground connected is active B 25 Aux Input 4 1 0mm2 Ground connected is active B 26 Aux Input 5 1 0mm2 Ground c...

Page 8: ...t 1 0mm2 Connected to S phase of mains 2A fuse recommended HGM7110N without 42 Mains T phase voltage monitoring input 1 0mm2 Connected to T phase of mains 2A fuse recommended HGM7110N without 43 Mains...

Page 9: ...The setting value is mains rated voltage percentage return value and delay value also can be set 8 Mains Under Voltage 0 200 80 9 Mains Over Frequency 0 200 Disabled The setting value is mains rated...

Page 10: ...conditions and inspecting engine speed Details to see the following installation description 3 Engine Rated Speed 0 6000 RPM 1500 Provide standard for judging over under speed and on load speed 4 Spe...

Page 11: ...higher than the setting value starter will disconnect Details to see the following installation description 19 Oil Pressure of Crank Disconnect 0 1000 kPa 200 When engine oil pressure is higher than t...

Page 12: ...ge Shutdown 0 200 80 10 Gen Over Frequency Shutdown 0 200 114 The setting values are rated frequency percentage of generator and delay value can be set 11 Gen Under Frequency Shutdown 0 200 80 12 Gen...

Page 13: ...de 0 2 0 0 Stop Mode 1 Manual Mode 2 Auto Mode 2 Communication Address 1 254 1 Controller address while in remote monitoring status 3 Communication Stop bit Setting 0 1 1 0 2 bit stop bit 1 1 bit stop...

Page 14: ...nected oil pressure sensor is lower than the setting point controller will initiate low oil pressure warning alarm judgment only starts after safety on delay expired Return value and delay value can b...

Page 15: ...panel are inactive except for and displays on the right side of the first line of LCD status page 7 Reserved 8 Idle Control Mode Under speed under frequency and under voltage are not protected in thi...

Page 16: ...HGM7100N GENSET CONTROLLER USER MANUAL HGM7100N Genset Controller 2017 08 26 Version1 0 Page 44 of 48 13 TYPICAL APPLICATION Figure 5 HGM7100N Typical Application Figure 6 HGM7120N Typical Application...

Page 17: ...ANUAL HGM7100N Genset Controller 2017 08 26 Version1 0 Page 45 of 48 Figure 7 Single Phase 2 Wire Connection Diagram Figure 8 2Phase 3Wire Connection Diagram NOTE Expand relay with high capacity in st...

Page 18: ...and negative input ports in order to prevent charge disturbing the controller s normal working a SPEED SENSOR INPUT Speed sensor is the magnetic equipment which be installed in starter and for detecti...

Reviews: