HGM7100N GENSET CONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 8 of 48
4
OPERATION
4.1
KEY FUNCTION
Table 3 - Key Function Descriptions
Icon
Function
Description
Stop/ Reset
Stop running generator in Auto/Manual mode;
In stop mode, in case of alarm condition, pressing the button will
reset alarm;
Pressing and holding the button for 3 seconds will test indicator
lights (lamp test);
During stopping process, press this button again to stop generator
immediately.
Start
Under manual mode, press this button will start genset;
Manual
Pressing this key will set the module into manual mode.
Auto
Pressing this key will set the module into auto mode.
C/O
Pressing this key to control breaker close or open in C/O interface
under manual mode.
(only suit for HGM7120N)
Close
Pressing this key to control breaker close under user manual mode.
(only suit for HGM7110N)
Open
Pressing this key to control breaker open under user manual mode.
(only suit for HGM7110N)
Set/Confirm
Pressing this key will enter into Main Menu;
In setting parameter status, press this key will shift cursor or confirm
setting value.
Up/Increase
Scrolls the screen up; Shift the cursor up or increase the set value
in parameter setting menu.
Down/Decrease
Scrolls the screen down; Shift the cursor down or decrease the set
value in parameter setting menu.
Homepage/Return
Controller returns to homepage if pressed this key in main screen;
controller returns to the previous page if pressed this key in
parameter setting page; hold and press this key for 3 seconds, trip
alarm can be reset.
Note: press any key to mute alarms in main screen.