![Smartgen HGM7100N Series User Manual Download Page 8](http://html1.mh-extra.com/html/smartgen/hgm7100n-series/hgm7100n-series_user-manual_1297521008.webp)
HGM7100N GENSET CONTROLLER USER MANUAL
HGM7100N Genset Controller 2017-08-26 Version1.0 Page 21 of 48
No.
Function
Cable Size
Remarks
38
Gen
W-phase
Voltage
Monitoring Input
1.0mm
2
Connected to W-phase output of genset (2A fuse
recommended).
39 Gen N2-line Input
1.0mm
2
Connected to N-line output of genset.
40
Mains
R-phase
Voltage
Monitoring Input
1.0mm
2
Connected to R-phase of mains (2A fuse recommended).
(HGM7110N without)
41
Mains
S-phase
voltage
monitoring input
1.0mm
2
Connected to S-phase of mains (2A fuse recommended).
(HGM7110N without)
42
Mains
T-phase
voltage
monitoring input
1.0mm
2
Connected to T-phase of mains (2A fuse recommended).
(HGM7110N without)
43 Mains line N1 Input
1.0mm
2
Connected to N-line of mains. (HGM7110N without)
44
RS485 Common Ground
0.5mm
2
120
Ω shielded wire is recommended with single end
ground.
45 RS485-
0.5mm
2
46 RS485+
0.5mm
2
47
VOUT(+5V)
0.5mm
2
Output DC +5V.
NOTE: USB ports in controller rear panel are programmable parameter ports, user can directly configure
the controller via PC.
NOTE: ETHERNET port in controller rear panel is network monitoring port, user can directly monitor the
controller via PC.