HGM6510 GENSET PARALLEL UNIT
HGM6510 Genset Parallel Unit
ISSUE 2013-07-15
Version 1.7
Page 43 of 52
Pin Function
Cable
Size
Description
6
Aux. Output 1
2.5mm
2
B+ output
,
rated 16A
7
Aux. Output 2
2.5mm
2
B+ output
,
rated 16A
8
Aux. Output 3
2.5mm
2
B+ output
,
rated 16A
9
Charger(D+)
1.0mm
2
Connected with charger
starter’s D+
terminal. Ground connected is not allowed.
10 Aux. Input 1
1.0mm
2
Digital input
11 Aux. Input 2
1.0mm
2
Digital input
12 Aux. Input 3
1.0mm
2
Digital input
13 Aux. Input 4
1.0mm
2
Digital input
14 Aux. Input 5
1.0mm
2
Digital input
15 Aux. Input 6
1.0mm
2
Digital input
16 Aux. Input 7
1.0mm
2
Digital input
17 Aux. Input 8
1.0mm
2
Digital input
18 Aux. Input 9
1.0mm
2
Digital input
19 Common GND(B-)
1.0mm
2
Connected with enclosure or negative of
starter battery.
20 Magnetic Pickup
1.0mm
2
Connect to speed sensor
21 Magnetic
1.0mm
2
22 Magnetic Pickup -
1.0mm
2
23 CAN J1939 SCR
0.5mm
2
Impedance-
120Ω
shielding
wire
is
recommended.
24 CAN J1939 (H)
0.5mm
2
25 CAN J1939 (L)
0.5mm
2
26 MSC SCR
0.5mm
2
Use 120Ω shielding wire to connect all
parallel HGM6510 controllers together.
27 MSC (H)
0.5mm
2
28 MSC (L)
0.5mm
2
29 GOV Wire B (+)
1.0mm
2
2-core shielded wire is recommended,
shielding layer connected to the ground at
GOV end.
30 GOV Wire A (-)
1.0mm
2
31 Not Used
32 AVR Wire B (+)
1.0mm
2
2-core shielded wire is recommended,
shielding layer connected to the ground at
AVR end.
33 AVR Wire A (-)
1.0mm
2
34 RS485 SCR
0.5mm
2
PC
programming
or
monitoring
port
(Opto-isolation); its single-end earthed.
35 RS485 A (-)
0.5mm
2
36 RS485 B (+)
0.5mm
2
37
38
39
Aux. Output 5
2.5mm
2
Normally open/close volts free contactor.
Rated 16A.
40
Aux. Output 4
2.5mm
2
Normally open volts free contactor. Rated
16A.
41
42
Bus A Phase Voltage
Sensing Input
1.0mm
2
Connected to A-phase of bus (2A fuse is
recommended)
43
Bus B Phase Voltage
Sensing Input
1.0mm
2
Connected to B-phase of bus (2A fuse is
recommended)