HGM6510 GENSET PARALLEL UNIT 

 

 

 

12.2  STEP 2: MANUAL PARALLEL OPERATION OFF-LOAD 

 

1)  Close  breaker  and  parallel  gensets  manually,  check  that  the  units  synchronization 

parallel is smooth and steady and breaker close impulse current is not too high; 

2)  After gensets parallel operation off load, check that there is no high circumfluence on 

HGM6510 current screen; 

3)  After  gensets  parallel  operation  off  load,  check  if  the  output  of  active  and  reactive 

power  is  equal  to  0;  if  it  is  not,  then  check  if  there  is  power  oscillation;  if  there  is, 

adjust the gain and stability values of HGM6510 controller, or adjust engine GOV or 

generator  AVR  gain  and  stability  potentiometer  to  avoid  active  and  reactive  power 

oscillation; output is close to 0. 

 

12.3  STEP 3: MANUAL PARALLEL OPERATION ON-LOAD 

 

1)  Parallel the gensets manually, perform on-load test and check if active and reactive 

power is evenly distributed between all the gensets; 

2)  Parallel  the  gensets  manually,  perform  ramp  on-load  test  to  see  if  there  is  high 

overshoot or power oscillation during this period; if there is, regulate Load Rampx%/s 

via PC software; 

3)  Parallel the gensets and on-load manually, perform ramp off-load test to see if gen-

set breaker opens after reaching minimum load threshold (%); 

4)  Parallel  the  gensets  manually,  perform  impact  load  test  and  impact  off-load  test  to 

check if there is power oscillation. 

 

12.4  STEP 4: FULLY AUTOMATIC PARALLEL OPERATION 

 

When  the  controller  is  in  auto  mode,  if  “remote  start  on-load  demand”  is  active,  it  will 
carry  out  fully  automatic  parallel  operation,  start  and  stop  according  to  the  users’ 

requirement. There are 3 ways of automatic parallel operation: 

1)  Start  on-load  demand:  the module  with  the highest  priority  starts firstly. When  load 

exceeds the pre-set start maximum percentage, the second according to the priority 

module will start the gen-set, synchronize and share load. When load falls lower than 

the preset minimum stop percentage, after stop delay the second module breaker will 

be open and the module will be cooled down and stopped. 

2)  Start all sets initially: all the modules start at the same time; the first module to reach 

load  condition  closes  first;  when  other  modules  reach  load  condition,  they 

synchronize one by one. After that the modules monitors the load; If load value   falls 

Summary of Contents for HGM6510

Page 1: ...HGM6510 Genset Parallel Unit USER MANUAL Smartgen Technology...

Page 2: ...NDSTOP ALARMS 23 7 PANEL CONFIGURATION 26 7 1 LCD DISPLAY 26 7 1 1 STATUS DISPLAY 26 7 1 2 ENGINE DISPLAY 27 7 1 3 GENERATOR DISPLAY 27 7 1 4 BUS DISPLAY 28 7 1 5 SYNCHRONIZATION DISPLAY 28 7 1 6 ALAR...

Page 3: ...MANUAL PARALLEL OPERATION ON LOAD 46 12 4 STEP 4 FULLYAUTOMATIC PARALLEL OPERATION 46 13 POWER MANAGEMENT MODE 48 14 TROUBLESHOOTING 49 15 TYPICAL WIRING DIAGRAMS 50 15 1 HGM6510 TYPICALWIRING DIAGRA...

Page 4: ...re load automatically it can be used to parallel with other HGM6510 controller HGM6510 controller also monitors the engine indicating the operational status and fault conditions accurately When abnorm...

Page 5: ...Split phase active power PA PB PC Unit kW Total phase active power P Unit kW Split phase reactive power RA RB RC Unit kVar Total phase reactive power P Unit kVar Split phase apparent power SA SB SC U...

Page 6: ...over voltage warn Start battery under voltage warn Over current shutdown Fail to start alarm Fail to stop alarm Emergency shutdown Close fault Open fault Oil pressure sensor open circuit alarm Revers...

Page 7: ...port 20 English letters or 10 Chinese characters maximum Close to activate open to activate configurable input port types normally open normally closed configurable output port types Custom logic outp...

Page 8: ...DC28V power supply output Configurable Relay Output 2 16A DC28V power supply output Configurable Relay Output 3 16A DC28V power supply output Configurable Relay Output 4 16A AC250V passive output Conf...

Page 9: ...urable LED Stop Mode Manual Mode Gen Closed Auto Mode Gen Normal Parameter Details Storage Conditions Temperature 40 85 C Protection Level IP55 Gasket Insulation Intensity Apply AC2 2kV voltage betwee...

Page 10: ...ey and controller enters in Auto mode Gen Closed In manual mode when busbar has voltage pressing the button will synchronize generator with bus and after that parallel generator with bus when busbar h...

Page 11: ...ng this cranking attempt then the fuel relay and start relay are disengaged for the pre set rest period crank rest time begins and wait for the next crank attempt NOTE If the unit has been configured...

Page 12: ...p the load from the generator to remaining set The Generator Breaker will open and the Cooling Delay is then initiated Should the Remote Start signal be re activated during the cooling down period the...

Page 13: ...atus is normal its indicator will be illuminated If generator voltage and frequency have reached on load requirements then the generator close relay will be energized genset will take load generator p...

Page 14: ...ill be displayed on LCD 3 Low Fuel Level Always active When the controller detects that the fuel level has fallen below the pre set value it will initiate a warning alarm and the corresponding alarm i...

Page 15: ...g alarm and the corresponding alarm information will be displayed on LCD 12 Gen Phase Sequence Wrong When generator is normal When the controller detects a phase rotation error correct phase is L1 L2...

Page 16: ...g alarm and the corresponding alarm information will be displayed on LCD 21 Over Speed Always active When the controller detects that the engine speed has exceeded the pre set value it will initiate a...

Page 17: ...a warning alarm and the corresponding alarm information will be displayed on LCD 29 Temperature Sensor Open Circuit Always active When the controller detects that the temperature sensor is open circu...

Page 18: ...sponding alarm information will be displayed on LCD 5 Under Speed From Waiting for load delay to Cooling delay When the controller detects that the generator speed has fallen below the pre set value i...

Page 19: ...played on LCD 14 Auxiliary Inputs 1 9 User defined When the controller detects that the auxiliary input 1 9 shutdown alarm signals it will initiate a shutdown alarm and the corresponding alarm informa...

Page 20: ...nitiate a shutdown alarm and the corresponding alarm information will be displayed on LCD 23 Reverse Power Always active If reverse power detection is enabled when the controller detects that the reve...

Page 21: ...value it will initiate a trip and stop alarm and the corresponding alarm information will be displayed on LCD 3 Loss Of Excitation Always active When the controller detects that the genset negative re...

Page 22: ...initiate a trip and stop alarm and the corresponding alarm information will be displayed on LCD 12 Mains ROCOF When mains parallel operation is enabled When the controller detects that the rate of cha...

Page 23: ...sponding alarm information will be displayed on LCD Note 1 Inverse Definite Minimum Time IDMT overcurrent delay decrease with the increase of overcurrent value Different overcurrent value has correspo...

Page 24: ...US 1 2 Second Status Screen UL N 0 V 0 0 A UL L 0V 0 00Hz Pf 0 00L 0 0 kW GeneratorAverage Phase Voltage Current Generator Average Line Voltage Frequency Generator Average Power Factor Total Active Po...

Page 25: ...rator Screen UL L 0 0 0 V UL N 0 0 0 V F 0 00Hz 0 RPM 3 phase Phase Voltage L1 N L2 N L3 N 3 phase Line Voltage L1 L2 L2 L3 L3 L1 Generator Frequency Engine Speed GENERATOR 3 2 Second Generator Screen...

Page 26: ...Percentage AVR Output Percentage GENERATOR 3 6 Sixth Generator Screen kWh 0000000 0 kVAh 0000000 0 kVarh 0000000 0 Total kW Energy Total kVA Energy Total kVar Energy GENERATOR 3 7 Seventh Generator S...

Page 27: ...dware Version Inner Temperature Issue Time 7 2 PARAMETER CONFIGURATION Press and hold and then press to enter into password screen Use and to increase decrease values and input the corresponding passw...

Page 28: ...10s Timer 10 Safety On Time 1 60 s 10s Timer 11 Over Speed Overshoot delay 0 10 s 2s Timer 12 Start Idle Time 0 3600 s 10s Timer 13 Warming Up Time 0 3600 s 30s Timer 14 Stop Delay 0 9999 s 30s Timer...

Page 29: ...ine speed 33 Under Speed Warn 1 5999 RPM 1350RPM On load value 1380RPM Setting standard Shutdown value Warn value On load value 34 Under Speed Shutdown 0 5998 RPM 1270RPM Under speed shutdown Value 35...

Page 30: ...between the generator and the bus If it is lower than the positive value and higher than the negative value then it is considered as synchronization 52 Negative Freq Difference 0 2 Hz 0 1Hz 53 Voltage...

Page 31: ...e Input 5 Indication close to activate Input 6 Working mode selection close to activate Input 7 Indication close to activate Input 8 Indication close to activate Input 9 Indication close to activate O...

Page 32: ...g the last digit and then press to save settings and exit Press without press to exit directly without saving Date and time order Year Month Date Week Hour Minute Second NOTE Parameters and the date t...

Page 33: ...enerator Total Active Reactive Apparent Energy Generator Phase Sequence Bus Phase Voltage L1 N L2 N L3 N Bus Line Voltage L1 L2 L2 L3 L3 L1 Bus Frequency Bus Phase Sequence 7 4 2 ECU DISPLAY Engine Oi...

Page 34: ...ore Inhibit In AUTO mode after the normal running of generator when the input is active automatic stop will not be allowed 6 Auto Start Inhibit In AUTO mode when the input is active automatic start wi...

Page 35: ...t is active priority is the highest used to select main standby generator 29 Reset Maintenance Alarm When the input is active the controller will reset maintenance time to its pre set value and clear...

Page 36: ...en set it is only responsible for synchronization power sharing schedule start stop and breaker opening closing 41 Reserved No Type Description 00 Output Not Used 01 Air Flap Relay Action when over sp...

Page 37: ...larm 024 Coolant Temp High Pre alarm for 1 Action when high water cylinder temperature warning alarm 025 Coolant Temp High Shutdown for 1 Action when high water cylinder temperature shutdown alarm 026...

Page 38: ...ns over frequency under frequency over voltage under voltage or auxiliary mains abnormal input is active 051 Mains High Frequency Action when mains over frequency 052 Mains High Voltage Action when ma...

Page 39: ...d shutdown 077 Reserved 078 Idle High Speed Control Action from Cranking delay to Start Idle delay and from Stop Idle delay to Fail to Stop delay 079 Pre oil Supply Output Action from Cranking delay t...

Page 40: ...oldest entry in the log so the log will always contain the 99 most recent abnormal events Pin Function Cable Size Description 1 B 2 5mm2 DC power supply negative input Connected with negative of start...

Page 41: ...c Pickup 1 0mm2 22 Magnetic Pickup 1 0mm2 23 CAN J1939 SCR 0 5mm2 Impedance 120 shielding wire is recommended 24 CAN J1939 H 0 5mm2 25 CAN J1939 L 0 5mm2 26 MSC SCR 0 5mm2 Use 120 shielding wire to co...

Page 42: ...5mm2 Outside connected to secondary coil of current transformer rated 5A 52 C T C Phase Sensing Input 2 5mm2 Outside connected to secondary coil of current transformer rated 5A 53 C T COM 2 5mm2 Outsi...

Page 43: ...LCD status screen 1 4 will display Module Number 3 See the picture on the right 3 Start the genset manually check if the engine and generator parameters are normal 4 Start the genset manually check if...

Page 44: ...t or power oscillation during this period if there is regulate Load Rampx s via PC software 3 Parallel the gensets and on load manually perform ramp off load test to see if gen set breaker opens after...

Page 45: ...le with lowest priority enters stop delay and then cools down and stops If load exceeds the preset start maximum percentage the generators that are at rest will all start again 3 Balanced engine runni...

Page 46: ...HGM6510 Genset Parallel Unit ISSUE 2013 07 15 Version 1 7 Page 48 of 52 HGM6510 GENSET PARALLEL UNIT 13 POWER MANAGEMENT MODE Power management mode can be selected via configurable input ports...

Page 47: ...esponding breaker and its wiring according to the information on LCD Check auxiliary input port Generator fails to close Check ATS auxiliary input port Check generator close relay Generator Reverse Ph...

Page 48: ...Parallel Unit ISSUE 2013 07 15 Version 1 7 Page 50 of 52 15 TYPICAL WIRING DIAGRAMS 15 1 HGM6510 TYPICAL WIRING DIAGRAM NOTE Expansion high capacity relays for start and fuel output ports are recommen...

Page 49: ...HGM6510 GENSET PARALLEL UNIT HGM6510 Genset Parallel Unit ISSUE 2013 07 15 Version 1 7 Page 51 of 52 15 3HGM6510 MULTI SET PARALLEL APPLICATION...

Page 50: ...through a modem communicate with controller and perform remote start stop data monitoring and other functions RS232 485 interface uses MODBUS communication protocol MODBUS is a master slave protocol...

Reviews: