After the starter motor has disengaged, the Safety On timer is activated, allowing
Oil Pressure, High Engine Temperature, Under-speed, Charge Fail and any
delayed Auxiliary fault inputs to stabilize without triggering the fault.
Once the engine is running, the Warm Up timer, if selected is initiated, allowing
the engine to stabilize before it can be loaded.
In
manual
mode, generator take load or no load depend on mains supply, if
mains is normal, it will not take load, otherwise it will take load.
In
manual test
mode, generator will take load regardless of mains supply normal
or abnormal.
●Hgm6110
: This manual mode is activated by pressing the
pushbutton. An
LED indicator beside the button confirms this action. In any of the two modes,
pressing the
pushbutton will initiate the start sequence.
The start sequence is similar as the above.
In above process, when the Warm Up timer has expired, if the remote start signal
is active, generator will take load, if inactive, generator will not take load.
In above process, pressing
key will bring the generator to a stop.
5. PROTECTION
5.1 WARN
Warns are non-critical alarm conditions and do not affect the operation of the
generator system, they serve to draw the operators attention to an undesirable
condition.
In the event of a warn, the module will display at the last screen of LCD.
Warn is shown as the below:
HIGH ENGINE TEMPERATURE
: if the module detects that the engine coolant
temperature has exceeded the high engine temperature setting level after the
Safety On timer has expired and the input of
Inhibit WTH stop
is activated, a
warn will occur.
LOW OIL PRESSURE
, if the module detects that the engine oil pressure has