Pin
Function
Dim
Description
17
Coolant Temperature
Input
Connect to Coolant Temperature
sender
18
Oil Pressure Input
Connect to Oil pressure sender
19
Fuel Level input
Connect to Fuel Level sender
Reference
table 4
20
Auxiliary input 1
1.0mm
Switch to -ve
21
Auxiliary input 2
1.0mm
Switch to -ve
Reference
table 3
22
Remote start input
1.0mm
Switch to -ve
23
CT Secondary for L1
2. 5mm
Connect to secondary of L1
monitoring CT
24
CT Secondary for L2
2. 5mm
Connect to secondary of L2
monitoring CT
25
CT Secondary for L3
2. 5mm
Connect to secondary of L3
monitoring CT
26
CT secondary common
2. 5mm
Connect to secondary of all
monitoring CT’s
27
Generator L1 voltage
monitoring
1. 0mm
Connect to Generator L1 output
(Recommend 2A fuse)
28
Generator L2 voltage
monitoring
1. 0mm
Connect to Generator L2 output
(Recommend 2A fuse)
29
Generator L3 voltage
monitoring
1. 0mm
Connect to Generator L3 output (
(Recommend 2A fuse)
30
Generator Neutral input
1. 0mm
Connect to Generator Neutral
terminal (AC)
31
Mains L1 voltage
monitoring
1. 0mm
Connect to mains L1 output
(Recommend 2A fuse)
32
Mains L2 voltage
monitoring
1. 0mm
Connect to mains L2 output
(Recommend 2A fuse)
33
Mains L3 voltage
monitoring
1. 0mm
Connect to mains L3 output
(Recommend 2A fuse)
34
Mains Neutral input
1. 0mm Connect to mains Neutral terminal
35
RS485 port Common
0. 5mm
36
RS485 port A(-)
0. 5mm
37
RS485 port B(+)
0. 5mm
Use only
120Ω
RS485 approved
cable
Note:
1. These terminals of 31, 32, 33, 34 are not used for HGM6110 module.
2. The terminal of LINK on the rear panel is an interface for upgrading module software.
3. Sensor sensing input. Connect to resistive type sender.