HGM6110/6120 AUTO START MODULE
HGM6110/6120 Auto Start Module ISSUE 2.0 2008-10-27 Page 17 of 24
Num Parameter
Range
Default Remark
51
OP disconnect
(0-400)kPa
200
When engine oil pressure is large
than
this
point,
starter
will
disconnect.
52
Select AC system
0 3P4L
1 2P3L
2 1P2L
0
3P4L(3 phase 4 wire)
53
Select temp curve
(0-8)
04
SGD(120
)
℃
54
Select press curve
(0-8)
04
SGD(10Bar)
55
Select level curve
(0-5)
0
Not used
7.2 OUTPUT 1-4 TABLE (TABLE 2)
Num
Content
Description
0
Not used
1
Common alarm
The designated programmable output relay will
energize when any warning or shutdown fault
circuit has been activated.
2
Energised to stop
The designated programmable output relay will
energize when a stop signal has been activated.
The output will remain energized for pre-set timer
once the engine has come to a complete stop, then
de-energizes.
3
Idle control
The designated programmable output relay will
energize when the idle delay is not zero. The
output contact would typically be connected to the
“idle/run” input control of an electronic governor.
4
Preheat control
The designated programmable output relay will
energize during the preheat delay timer period and
also energize until the engine receive a crank
success signal. The preheat output is typically
used for an engine starting aid such as glow plugs.
5
Close Gens
Switch generator breaker on.
6
Close mains
Switch mains breaker on.(HGM6120)
7
Open ATS
Switch breaker off. The output delay is 3 seconds.
8
Raise speed control
It’s active from entering warming to switching load
on.
9
Drop speed control
It’s active from idling in stopping to engine has
been stopped.
10
Reserve
7.3 DIGIT INPUT 1-2 TABLE (TABLE 3)
Num
Content
Description
0
Not used