HGM6100N-RM REMOTE MONITORING MODULE USER MANUAL
HGM6100N-RM Remote Monitoring Module 2019-08-06 Version 1.0 Page 10 of 14
5 CONNECTIONS
HGM6100N-RM lacks a mains voltage 3-phase input terminal comparing with HGM6120N-RM.
HGM6120N-RM back panel is as below.
Fig. 3 Controller Back Panel
Table 4 Wiring Terminal Connection Descriptions
No.
Function
Cable Size
Description
1
DC input B-
2.5mm
2
Connected to negative of starter battery
2
DC input B+
2.5mm
2
Connected to positive of starter battery. If wire
length is over 30m, double the wires in parallel.
Max. 20A fuse is recommended.
3
Emergency Stop
2.5mm
2
NOTE
: HGM6100N-RM doesn't have the functions.
4
Fuel
1.5mm
2
5
Crank
1.5mm
2
6
Aux. Output 1
1.5mm
2
7
Aux. Output 2
1.5mm
2
8
9
10
Aux. Output 3
2.5 mm
2
11
12
Aux. Output 4
2.5mm
2