HGM6100N-RM REMOTE MONITORING MODULE USER MANUAL 

HGM6100N-RM Remote Monitoring Module            2019-08-06          Version 1.0          Page 4 of 14 

1 OVERVIEW 

HGM6100N-RM

 is remote monitoring module designed for HGM6100N series genset controllers. 

With RS485 port it can realize functions of remote start/stop, data measuring, and alarm display etc. 

it is applicable for single remote monitoring system. It can be in the monitoring mode, realizing only 

monitoring,  not  controlling,  or  it  can  be  changed  over  to  remote  control  mode  by  local  module 

transfer, monitored and controlled remotely.   

HGM6100N-RM

  remote  monitoring  module  uses  micro-processing  technique  and  132

 

x64  LCD 

display.    8  kinds  of  languages  are  optional  (Simplified  Chinese,  English,  Spanish,  Russian, 

Portuguese, Turkish, Polish and French) and can be changed freely. It can be widely used in all 

types of automatic control system with compact structure, simple connections and high reliability. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for HGM6100N-RM

Page 1: ...HGM6100N RM REMOTE CONTROL MODULE USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD ...

Page 2: ... 14 CONTENT 1 OVERVIEW 4 2 PERFORMANCE AND CHARACTERISTICS 5 3 SPECIFICATION 6 4 OPERATION 7 4 1 KEY DSCRIPTIONS 7 4 2 CONTROLLER PANEL 8 4 3 REMOTE CONTROL MODE OPERATION 9 5 CONNECTIONS 10 6 TYPICAL APPLICATION 12 7 INSTALLATION 13 7 1 FIXING CLIPS 13 7 2 OVERALL DIMENSION AND PANEL CUTOUT 13 8 TROUBLESHOOTING 14 ...

Page 3: ...hts reserved No part of this publication may be reproduced in any material form including photocopying or storing in any medium by electronic means or other without the written permission of the copyright holder Applications for the copyright holder s written permission to reproduce any part of this publication should be addressed to Smartgen Technology at the address above Any reference to tradem...

Page 4: ...onitoring system It can be in the monitoring mode realizing only monitoring not controlling or it can be changed over to remote control mode by local module transfer monitored and controlled remotely HGM6100N RM remote monitoring module uses micro processing technique and 132 x64 LCD display 8 kinds of languages are optional Simplified Chinese English Spanish Russian Portuguese Turkish Polish and ...

Page 5: ... to modify the settings and at the same time they shall be stored in internal FLASH memory so that the parameters won t be lost in case of power outage All parameters can be set from the front panel but also can be adjusted by RS485 interface via PC All parameters of HGM6100N RM must be configured as same as that of local module of HGM6100N controller Wide power supply range 8 35 V DC accommodatin...

Page 6: ...continuous Power Consumption 3W Standby mode 2W Overall Dimensions 209 mm x 166 mm x 45mm Panel Cutout 186mm x 141mm Working Condition Temperature 25 70 º C Humidity 20 93 RH Storage Condition Temperature 30 80 º C Protection Level Front panel IP55 Insulation Intensity Apply AC2 2kV voltage between high voltage terminal and low voltage terminal and the leakage current is not more than 3mA within 1...

Page 7: ...ler shall be put in the auto mode Close Open Under manual mode press it and breaker close open can be controlled NOTE It is only applicable for HGM6120N RM Series Close Under manual mode press it and breaker close can be controlled NOTE It is only applicable for HGM6110N RM Series Open Under manual mode press it and breaker open can be controlled NOTE It is only applicable for HGM6110 RM Series Se...

Page 8: ... HGM6110N RM Front Panel Indicators Fig 2 HGM6120N RM Front Panel Indicators NOTE Parts of Indicators Descriptions Alarm Indicator slowly flashes for warning alarms quickly flashes for shutdown alarms light off for none alarms Status Indicator Light off for standby status genset flashes once in start stop process always light on for normal running ...

Page 9: ...nput is active on local module the 4th line of LCD displays remote mode on both remote module and local module which means remote control mode is active After remote mode is active genset mode transfer and genset start stop operations can be conducted NOTE if alarms occur in start stop process corresponding alarm information will be synchronously displayed on the LCD of HGM6100N RM ...

Page 10: ... Table 4 Wiring Terminal Connection Descriptions No Function Cable Size Description 1 DC input B 2 5mm2 Connected to negative of starter battery 2 DC input B 2 5mm2 Connected to positive of starter battery If wire length is over 30m double the wires in parallel Max 20A fuse is recommended 3 Emergency Stop 2 5mm2 NOTE HGM6100N RM doesn t have the functions 4 Fuel 1 5mm2 5 Crank 1 5mm2 6 Aux Output ...

Page 11: ...2 24 IB 1 5mm2 25 IC 1 5mm2 26 ICOM 1 5mm2 27 U 1 0mm2 28 V 1 0mm2 29 W 1 0mm2 30 N2 1 0mm2 31 R 1 0mm2 32 S 1 0mm2 33 T 1 0mm2 34 N1 1 0mm2 35 RS485 SCR Impedance 120Ω shielding wire is recommended single end is ground connected 36 RS485 0 5mm2 37 RS485 0 5mm2 38 Aux Input 4 1 0mm2 NOTE HGM6100N RM doesn t have the functions 39 Aux Input 5 1 0mm2 40 Sensor COM 1 0mm2 41 CAN SCR 0 5mm2 42 CAN L 0 ...

Page 12: ...6100N RM REMOTE MONITORING MODULE USER MANUAL HGM6100N RM Remote Monitoring Module 2019 08 06 Version 1 0 Page 12 of 14 6 TYPICAL APPLICATION Fig 4 HGM6100N RM and HGM6100N CAN Typical Application Diagram ...

Page 13: ...troller panel Care should be taken not to over tighten the screws of fixing clips 7 2 OVERALL DIMENSION AND PANEL CUTOUT Fig 5 Case Dimensions and Cutout HGM6100N RM controller can be applicable for 8 35 V DC battery voltage environment Battery negative must be reliably connected to engine shell The connection wire between controller power and battery negative and positive should not be less than ...

Page 14: ...SHOOTING Table 5 Troubleshooting Symptom Measures No response with power on Check starter battery Check controller wire connections Check DC fuse Abnormal communication of controller Check whether RS485 A and B are connected reversely Adding 120Ω resistance is recommended between RS485 A and B ______________________________________ ...