HAT600R Series ATS Controller User Manual Page 46 of 59
14
ATS SUPPLY POWER
14.1
DC SUPPLY
Configure switch power supply to DC supply. When switch is DC supply, it is considered that switch can
be transferred at any time, including the time of S1/S2 power off.
14.2
AC SUPPLY
If AC supply is used, ATS power is supplied by controller smartly. If there is only one voltage normal, it
can ensure ATS power supply normal and make it normally transfer.
Please confirm the following parameters when AC supply is used:
14
Switch supply type is AC supply;
15
The upper and lower thresholds of AC supply voltage meets requirements;
16
ATS supply power of output port setting is phase voltage or line voltage.
For example: taking ATS power supply as phase voltage (A-N):
Set AC supply rated voltage to 220V, and set AC supply voltage lower limit to 70% rated, upper limit to
130% rated. Set configurable output 1 to "ATS power L1", and set configurable output 2 to "ATS power
N".
Connect phase voltage L1 of S1 and S2 to N/C terminal 5 and N/O terminal 7 of configurable output 1,
connect phase N of S1 and S2 to N/C terminal 8 and N/O terminal 10 of configurable output 2, and then
connect COM of output 1 and output 2 to ATS supply power. Connecting method is as below:
Fig. 12 ATS Power Phase Voltage Supply
When ATS power is line voltage supply, the setting method is as above. The only thing needs to do is
change N phase to line voltage. Change configurable output 2 based on the setting. Reset upper and
lower limits of AC supply voltage based on rated voltage. Connecting method is as below:
Fig. 13 ATS Power Line Voltage Supply
NOTE 1
: N/C terminal voltage must be S1 voltage.
NOTE 2
: Only when controller detects ATS power normal, can it issue switch close/open actions. If
output port is not set for ATS power, system default is to make L1-N supply for ATS power.