HAT600R Series ATS Controller User Manual Page 22 of 59
9
PARAMETER SETTINGS
9.1
ILLUSTRATION
In the first page of the main screen, press
key and enter menu page. Select "1. Configuration",
and press
to confirm, so it enters parameter setting password interface. Input correct password
to enter parameter main screen. If password is wrong, it directly returns back to main screen.
Default
factory password: 01234.
In parameter configuration screen, press
key to return to the previous
directory.
9.2
PARAMETER CONFIGURATION LIST
Table 18 Parameter Setting Items
No.
Item
Range
Default
Description
AC Settings
1
S1 Available Delay
(0-3600)s
10
The check time for S1 from abnormal to
normal;
2
S1 Unavailable Delay (0-3600)s
5
The check time for S1 from normal to
abnormal;
3
S2 Available Delay
(0-3600)s
10
The check time for S2 from abnormal to
normal;
4
S2 Unavailable Delay (0-3600)s
5
The check time for S2 from normal to
abnormal;
5
Master-Slave Set
(0~1)
0
0: S1 Master
1: S2 Master
6
System Type Set
(0~3)
0
0: S1 Mains S2 Gen
1: S1 Gen S2 Mains
2: S1 Mains S2 Mains
3: S1 Gen S2 Gen
7
AC System
(0-3)
0
0: 3-Phase 4-Wire
1: 3-Phase 3-Wire
2: 2-Phase 3-Wire
3: Single Phase 2-Wire
8
PT Fitted
(0~1)
0
0: Disable
1: Enable
9
PT Primary Voltage
(30~35000)V
100
Primary voltage of AC PT ratio;
10
PT Secondary
Voltage
(30~1000)V
100
Secondary voltage of AC PT ratio;
11
Rated Voltage
(0-35000)V
220
Rated voltage of AC system;
12
Over Volt Set
(0~1)
1
0: Disable
1: Enable
13
Set Value
(0-200)%
120
Upper limit value of voltage; it is
abnormal if the value has exceeded the
set value.
14
Return Value
(0-200)%
115
Upper limit return value of voltage; it is
normal only when the value has fallen
below the set value.
15
Under Volt Set
(0~1)
1
0: Disable
1: Enable
16
Set Value
(0-200)%
80
Lower limit value of voltage; it is
abnormal if the value has fallen below
the set value.
17
Return Value
(0-200)%
85
Lower limit return value of voltage; it is
normal only when the value has
exceeded the set value.
18
Rated Frequency
(10.0-75.0)Hz
50.0
Rated frequency of AC system