HAT163 ATS CONTROLLER USER MANUAL
HAT163 ATS Controller 2018-05-20 Version 1.0 Page 9 of 21
No.
Items
Function Description
Remark
7
B1
2-phase 3-wire: connect with A1, B1, and N1; C1
is not connected;
3-phase 3-wire: connect with A1, B1, and C1; N1
is not connected (special order required).
8
A1
9
Gen Start
Signal Output
Volt free normally close
contact output
Rated capacity:
AC7A/250V
10
11
COM
Breaker close/open output
common port
12
1# Close Relay
Volt free normally open
contact output
Rated capacity:
10A/250VAC
13
2# Close Relay
Volt free normally open
contact output
Rated capacity:
10A/250VAC
14
Open Output
Volt free normally open
contact output
Rated capacity:
7A/250VAC
15
NO
Rated capacity:
10A/250VAC
16
LO
Rated capacity:
10A/250VAC
17
FO IN
Force open input, when
active, transfer ATS to
breaking position.
Ground is active
18
1# Close Input
Detect 1# breaker close
status, auxiliary contact
input.
Ground is active
19
2# Close Input
Detect 2# breaker close
status, auxiliary contact
input.
Ground is active
20
Common Port
GND
LINK
Communication
Port
Communicate with PC and
used for program update
Used with SG72 adaptor
F1
Fuse
Rated 10A 250VAC
F2
Fuse
Rated 10A 250VAC