3. SPECIFICATION
Table 2
– Specification Parameters
Items
Contents
Operating Voltage
AC power A1N1/A2N2 supply.
Rated 240VAC (range: AC170V~AC277V)
Power Consumption
Under rated voltage, power consumption is not more than 3VA
AC Voltage Input:
3-phase 4-wire
2-phase 3-wire
Single phase 2-wire
3-phase 3-wire
AC170V
– AC277V (ph-N)
AC170V
– AC277V (ph-N)
AC170V
– AC277V (ph-N)
AC170V
– AC277V (ph-ph) (special order required)
AC Frequency
50/60Hz
1# Close Relay
10A/250VAC Volt free output (Normally open)
2# Close Relay
10A/250VAC Volt free output (Normally open)
Breaker Open Relay
7A /250VAC Volt free output (Normally open)
Oil Engine Start Relay
7A /250VAC Volt free output (Normally close)
LO/NO Relay
10A/250VAC Active output
Communication
LINK interface, MODBUS-RTU Protocol
Case Dimensions
86.9mmx158mmx119.5mm
Panel Cutout
73.5mmx144mm
Working Conditions
Temperature: (-25~+70)°C; Relative Humidity: (20~93)%RH
Storage Condition
Temperature: (-25~+70)°C
Protection Level
IP65: when water-proof gasket installed between control panel and
enclosure.
Isolation Strength
Apply AC1.5kV voltage between high voltage terminal and low voltage
terminal;
The leakage current is not more than 3mA within 1min.
Weight
0.7kg