Longo programmable controller LPC-2.IR2V
4 OPERATION
LPC-2.IR2V can be in one of two operational modes - normal or error. When LPC-2.IR2V is in normal
mode, module parameters can be read or written via Smarteh IDE software.
4.1 Operational modes
Normal
Communication with the main module is working. Only green “PWR” LED2 is turned on.
Error
In case of communication fault, red “ERR” LED1 will turn on.
4.2 Parameters
If parameter is set to logical “1”, is considered to be active, enabled or set. If parameter has logical
value “0” is considered to be inactive, disabled or cleared.
Parameter can be a command or feedback. When parameter is marked as feedback it means that
LPC-2.IR2V is sending information to the main module. On the other hand, command represents
request from the main module to the LPC-2.IR2V.
Command:
IR command number selection for transmit
[oIrCmdSendNum]
:
This parameter is used to
select the IR learned command which will be used for transmit.
Type: WORD
Raw to engineering data:
1 .. 15 IR transmit command 1 .. IR transmit command 15
→
IR command transmit control bit
[oIrCmdSend]
:
When this bit goes to "1", selected IR
command in o
IrCmdSendNum
is transmitted.
Type: BOOL
Raw to engineering data:
“0” No transmit
→
“1” Transmit selected IR command
→
IR protocol selector
[oIrProtocolSel]
:
Selector for IR protocol.
Type: WORD
Raw to engineering data:
0 Learned IR commands (Receive and transmit)
→
1 RC-5 IR protocol (Receive only)
→
2 Daikin (Transmit only)
→
3 Toshiba (Transmit only)
→
4 Hitachi (Transmit only)
→
5 Panasonic (Transmit only)
→
6 Mitsubishi (Transmit only)
→
IR Off/On command
[oIrOffOn]
:
IR command for Off or On is transmitted when
oIrCmdSend
is set.
Applicable only when protocol selector is set to 2 .. 6.
Type: BOOL
Raw to engineering data:
“0” IR set Off command
→
“1” IR set On command
→
4