3.2 Mounting instructions

Figure 3: Housing dimensions

Dimensions in milimeters.

EXTERNAL SWITCH OR CIRCUIT-BREAKER AND EXTERNAL OVERCURRENT
PROTECTION: The unit is allowed to be connected to installation with
over current protection that has nominal value of 16 A or less.

RECOMMENDATION   ON   SWITCH   OR   CIRCUIT-BREAKER   PROTECTION:
There should be two poles main switch in the installation in order to
switch   off   the   unit.   The   switch   should   meet   the   requirements   of
standard IEC60947 and have a nominal value at least 6 A. The switch
or   circuit-breaker   should   be   within   easy   reach   of   the   operator.   It
should be marked as the disconnecting device for the equipment.

All connections, module  attachments and  assembling  must be done
while module is not connected to the main power supply.

5

3

6

 

60 

18 

9

0

 

9

5

 

Summary of Contents for LPC-2.DD2

Page 1: ...USER MANUAL Longo programmable controller LPC 2 DO4 Triac Output module Version 6 SMARTEH d o o Poljubinj 114 5220 Tolmin Slovenia Tel 386 0 388 44 00 e mail info smarteh si www smarteh si...

Page 2: ...Longo programmable controller LPC 2 DO4 Written by SMARTEH d o o Copyright 2005 SMARTEH d o o User Manual Document Version 6 June 2019 i...

Page 3: ...ot include damage due to transport or because of unconsidered corresponding regulations of the country where the module is installed This device must be connected properly by the provided connection s...

Page 4: ...r LPC 2 DO4 Longo programmable controller LPC 2 DO4 1 DESCRIPTION 1 2 FEATURES 2 3 INSTALLATION 3 3 1 Connection scheme 3 3 2 Mounting instructions 5 3 3 Module labeling 7 4 TECHNICAL SPECIFICATIONS 8...

Page 5: ...ut module It can be used in a wide range of operation LED indicates triac output contacts state If it is on the module s connection pins are shorted refer to the Table 5 Module is powered from interna...

Page 6: ...DO4 2 FEATURES Figure 1 LPC 2 DO4 module Table 1 Technical data Snubberless zero crossing triac output also suitable for use with inductive loads Long life AC digital output Small dimensions and stan...

Page 7: ...tput 24 230 V AC Make contact triac output NO Table 3 K1 Internal BUS Data DC power supply Connection to I O module Table 4 K2 Internal BUS Data DC power supply Connection to I O module 1 Wires connec...

Page 8: ...tal output state On triac on conductive Off triac off non conductive NOTE Special care must be taken in case of high inductance loads e g Relays or contactors High inductance load may cause output fai...

Page 9: ...MMENDATION ON SWITCH OR CIRCUIT BREAKER PROTECTION There should be two poles main switch in the installation in order to switch off the unit The switch should meet the requirements of standard IEC6094...

Page 10: ...scheme in Figure 2 5 Switch ON main power supply Dismount in reverse order For mounting dismounting modules to from DIN rail a free space of at least one module must be left on the DIN rail NOTE LPC 2...

Page 11: ...e code 04 year of code opening 001 derivation code 001 version code reserved for future HW and or SW firmware upgrades 3 D C 16 05 is the date code 16 week and 05 year of production Label 2 descriptio...

Page 12: ...triac make contacts NO Output current 0 05 1 8 A continuous load Connection type screw type connector for stranded wire 0 75 to 2 5 mm2 Dimensions L x W x H 90 x 18 x 60 mm Weight 50 g Ambient tempera...

Page 13: ...following table describes all the changes to the document Date V Description 14 6 2019 6 Additional note added 1 7 2012 5 CGP General update 11 5 2010 4 Updated warranty permanence 30 6 2005 3 The in...

Page 14: ...Longo programmable controller LPC 2 DO4 6 NOTES 10...