SMAR if303 Operation, Maintenance & Instruction Manual Download Page 1

Summary of Contents for if303

Page 1: ......

Page 2: ...web www smar com contactus asp www smar com Specifications and information are subject to change without notice Up to date address information is available on our website smar...

Page 3: ...tional digital communications are known from existing smart transmitter protocols Higher accuracy multi variable access remote configuration and diagnostics and multi dropping of several devices on a...

Page 4: ...nel are allowed to participate in the activities of mounting electrical connection startup and maintenance of the equipment Qualified personnel are understood to be the persons familiar with the mount...

Page 5: ...RIBUTES 3 4 IF303 CYCLIC CONFIGURATION 3 5 HOW TO CONFIGURE THE ANALOG INPUT BLOCK 3 9 HOW TO CONFIGURE THE TOTALIZER BLOCK 3 11 CURRENT TRIM 3 13 VIA LOCAL ADJUSTMENT 3 14 TRANSDUCER DISPLAY CONFIGUR...

Page 6: ...IF303 Operation and Maintenance Instruction Manual VI...

Page 7: ...signal s in Fieldbus Start No Yes Is the indication correct See section 4 Maintenance OK Install the converter on the field following the instructions below Check the area classification and its prac...

Page 8: ...IF303 Operation and Maintenance Instruction Manual VIII...

Page 9: ...d to the minimum necessary since each time it is removed the circuits are exposed to the humidity The electronic circuit is protected by a humidity proof coating but frequent exposures to humidity may...

Page 10: ...the same bus must use the same signaling Various types of Fieldbus devices may be connected on the same bus The IF303 is powered via the bus The limit for such devices is according to the DP PA coupl...

Page 11: ...ed sealing methods The unused outlet connection should be plugged and sealed accordingly Should other certifications be necessary refer to the certification or specific standard for installation limit...

Page 12: ...Bus Topology Analog Ground Coupler Terminator Enabled Junction Box Terminator Figure 1 5 Tree Topology Intrinsic Safety Barrier When the Fieldbus is in an area requiring intrinsic safety a barrier mu...

Page 13: ...arate unit or from another device such as a controller or DCS The voltage should be between 9 to 32 Vdc for non intrinsic safe applications A special requirement applies to the power supply used in an...

Page 14: ...er Supply TR TR TR TR Transmitter 0 20mA 0 20mA 0 20mA 4 wire 0 20mA Transmitters or 0 20mA Current Generator CHANNEL1 CHANNEL 2 CHANNEL 3 COMMON Figure 1 7 Connection Avoid routing input wiring close...

Page 15: ...ement and operation of block execution self diagnostics and communication The program is stored in Flash memory For temporary storage of data there is a RAM The data in the RAM is lost if the power is...

Page 16: ...IRMWARE DOWNLOAD INTERFACE LOCAL ADJUST CPU EEPROM FLASH RAM MODEM POWER ISOLATION DISPLAY CONTROLLER S I G N A L I S O L A T I O N Resistor Shunt 3 x 100R Figure 2 2 IF303 Block Diagram WARNING Apply...

Page 17: ...rization temperature compensation control and exchange data to from hardware How to Configure a Transducer Block The transducer block has an algorithm a set of contained parameters and a channel conne...

Page 18: ...Checking User Current Characterization mA Scale In 100 10 100 Factory Trim User Trim Secondary value 1 AI Channel Secondary Value 2 SQR Root Scale Out 100 Scale Out 10 10 100 Primary Value AL Channel...

Page 19: ...om linear to square root function The input has to be done in percent of flow MAINT_DATE The date of last maintenance EEPROM_FLAG This parameter is used to indicate EEPROM saving process FACTORY_GAIN_...

Page 20: ..._VALUE This parameter contains the sensor value after the trim processing Unit derives from SENSOR_UNIT XD_ERROR Indicates the condition of calibration process according to 16 Default value set 22 App...

Page 21: ...S 4 r w C a 0 O B 46 ORDERING_CODE Array Unsigned 8 S 50 r w C a O B Table 3 2 Parameter Attribute IF303 CYCLIC CONFIGURATION The PROFIBUS DP and PROFIBUS PA protocols have mechanisms against communi...

Page 22: ...configuration tool usually called BMP After choosing the master define the baud rate for the network Do not forget that couplers may work with the following baud rate 45 45 kbits s Siemens model 93 7...

Page 23: ...many parameters of the Input Transducer block Figure x xx Function and Transducers Blocks Figure 3 2 Function and Transducers Blocks The device was created as IF303 As you can see the Transducer and D...

Page 24: ...Z Y I Q Q Z 10 Z Square Root Low_Flow_Cut_Off Y I Y 10 I Figure 3 4 Square Root Calculation When the user chooses Square Root he needs to configure more two parameters Low Flow Cutoff and Flow Lin Sqr...

Page 25: ...please see the Function Blocks Specifications To configure the Analog Input Block in offline mode please go to the main menu and select Device Offline Configuration Analog Input Block Using this windo...

Page 26: ...please go to the main menu and select Device Online Configuration Analog Input Block Mode The user can choose between 3 Analog Input Blocks Figure 3 7 Simatic PDM Online Configuration for Analog Inpu...

Page 27: ...ck execution The TOTAL is the totalized quantity The engineering unit used in the output is the UNIT_TOT The unit of the output must be compatible with the unit of the input provided by the transducer...

Page 28: ...n terms of online configuration for the Totalizer Block please go to the main menu and select Device Online Configuration Totalizer we have the following windows Figure 3 10 Simatic PDM Online Configu...

Page 29: ...he output Trim in one point is independent from the other There are at least two ways of doing the trim using local adjustment or using a Configuration Tool see below examples using Simatic PDM from S...

Page 30: ...y means of parameter BACKUP_RESTORE using option Last Cal Backup Via Local Adjustment The IF303 has 3 input transducers and its device leaves SMAR with factory settings The factory setting establishes...

Page 31: ...is performed Limit Conditions for Calibration For every writing operation in the transducer blocks there is a code indication for the operation associated with the writing method These codes appear i...

Page 32: ...same methodology to handle with it So since the user has learned once he is capable to handle all kind of field devices from SMAR All function block and transducers defined according Profibus PA have...

Page 33: ...ion option is selected then the display will show the increment and decrement arrows Set Alpha Numerical These parameters include two options value and mnemonic In option value it is possible to displ...

Page 34: ...will be shown at the LCD Always on the LCD interface will be shown two parameters at the same time switching between the configured parameter at the LCD II and the last monitoring parameter If the us...

Page 35: ...take a detailed look at this manual in the chapter related to Programming Using Local Adjustment It is significantly the resources on this transducer display also all the Series 303 field devices fro...

Page 36: ...Adjustment Holes Table 3 4 shows the actions on the Z and S holes on the FY303 when Local Adjustment is enabled HOLE ACTION Z Inicializes and rotates through the available functions S Selects the func...

Page 37: ...etics sc rew driver in s pan hole 4 Wait 3 seconds then MD will appear on display Browse Insert magnetic screw driv er in zero hole and hold Select Insert magnetic screw driv er in span hole and hold...

Page 38: ...e local adjustment programming tree is enabled and then important block parameters can be adjusted and communication can be pre configured via local adjustment MAIN BOARD WR J1 OFF ON W1 LOC ADJ OFF O...

Page 39: ...y insert the magnetic tool in orifice S as soon as lower is shown on the display An arrow pointing upward increment the value and an arrow pointing downward decrement the value Apply the 4 00 mA curre...

Page 40: ...pward increments the address and an arrow pointing downward decrements the address In order to increment the address insert the tool in S up to set the value desired In order to decrement the address...

Page 41: ...The voltage at the IF303 Fieldbus terminals must be between 9 and 32 VDC Electronic Circuit Failure Check the boards for defect by replacing them with spare ones No Communications Network Connections...

Page 42: ...wait for the 5 symbol on the right upper corner of the display to unlit thus indicating the end of the operation This operation has factory configuration that eliminates possible problems with the fun...

Page 43: ...ain boards you must do a trim to guarantee precision of the inputs With mismatched boards the factory trim will not be as good as it was Exploded View 1 2 3 4 5 6 7 8 9 10 12 13 15 11 14 16 Figure 4 1...

Page 44: ...al Adjustment Protection Cap 10 204 0114 Identification Plate Fixing Screw 11 204 0116 Terminal Insulator 12 314 0123 External Ground Screw 13 204 0124 Housing in Aluminium 14 304 0119 Terminal Holdin...

Page 45: ...justment magnetic tool if device is fitted with display Complete configuration is possible using PC software interface by using a configurator Performance Specifications Accuracy 0 03 of span for 4 20...

Page 46: ...FIELDBUS CONVERTER C D Local Indicator 0 1 Without Digital Indicator With Digital Indicator C D Mounting Bracket for 2 Pipe Mounting 0 1 2 Without Bracket Carbon Steel Bracket 316 SST Bracket C D Ele...

Page 47: ...L LISTING 3 ASSOCIATED APPARATUS GROUND BUS TO BE INSULATED FROM PANELS AND MOUNTING ENCLOSURES 4 ASSOCIATED APPARATUS GROUND BUS RESISTANCE TO EARTH MUST BE SMALLER THAN 1 ONE OHM 5 OBSERVE TRANSMITT...

Page 48: ...IF303 Operation and Maintenance Intruction Manual 5 4...

Page 49: ...presents in the area Without interference Temperature Vibration Others ______________________________ Ambient Temperature From __________ C up to __________ C OCCURRENCE DESCRIPTION _________________...

Page 50: ...office informing the defective instrument s serial number and return it to our factory In order to expedite analysis and solution of the problem the defective item should be returned with a descripti...

Page 51: ...operational limits temperature humidity etc according to the instructions manual In addition this Warranty Certificate excludes expenses with transportation freight insurance all of which are the cust...

Page 52: ...epair and SMAR and its dealer reserve themselves the right to refuse the service in cases not compliant to those conditions It is the customer s responsibility to tell SMAR and its dealer when the pro...