DFI302 – User’s Manual
11.4
PARAMETER
VALID RANGE/
OPTIONS
DEFAULT
VALUE
DESCRIPTION
ST_REV
0
TAG_DESC
Spaces
STRATEGY
0
ALERT_KEY
1 to 255
0
MODE_BLK
O/S
BLOCK_ERR
MEDIA
0:Serial, 1:TCP/IP
Serial
Define Modbus channel type.
MASTER_SLAVE
0:Master, 1:Slave
Slave
Define if DFI is master or slave.
DEVICE_ADDRESS
0-247
1
Define the DFI Modbus address (only for DFI slave).
BAUD_RATE
0:110, 1:300, 2:600, 3:1200,
4:2400, 5:4800, 6:9600,
7:19200, 8:38400, 9:57600,
10:115200
19200
Define the baud rate (only for media serial).
STOP_BITS
0:1, 1:2
1
Define the number of stop bits (only for media serial).
PARITY
0:None, 1:Even, 2:Odd.
Even
Define the parity (only for media serial).
TIMEOUT 0-65535 1000
Time to wait a response from a slave (for DFI master) or time to wait
the OUTs be updated (for DFI slave). Value 0 is used to disable.
NUMBER_RETRANSMISSIONS
0-255
1
Number of retransmission if DFI doesn’t receive response from slave.
SLAVE_ADDRESSES
IP number and Modbus addresses of slaves ( only for DFI master in
TCP/IP media);
RESTART_MODBUS
FALSE
Indicate if after communication fail in the slave, there will be a new
transmission after the time defined in TIME_T
O_
RESTART (only for
DFI master).
TIME_T
O_
RESTART
1-65535
1
Time to restart communication with slave
RTS_CTS
FALSE
Enable or disable handshaking.
ON_APPLY
0:None, 1: Apply
None
Apply the changes made in the Modbus blocks.
UPDATE_EVT
This alert is generated by any change to the static data.
BLOCK_ALM
The block alarm is used for all configuration, hardware, connection
failure or system problems in the block. The cause of the alert is
displayed in the subcode field. The first alert to become active will set
the Active status in the Status attribute. As soon as the Unreported
status is cleared by the alert reporting task, another block alert may
be reported without clearing the Active status, if the subcode has
changed.
When using the RS-232, install the DF58 module (RS-232/RS-485 Interface Module) if it is
necessary to communicate with more than one Modbus instrument, that is, in a Multipoint Network.
Refer to chapter “Adding Interfaces”.
3) Now, create the other blocks. The Modbus available blocks are: MBSS (Modbus Supervision
Slave), MBSM (Modbus Supervision Master), MBCS (Modbus Control Slave) and MBCM
(Modbus Control Master).
Summary of Contents for DFI302
Page 1: ...D F I 3 0 2 M E FEB 05 FOUNDATION...
Page 4: ...DFI302 User s Manual IV...
Page 6: ...DFI302 User s Manual VI...
Page 30: ...DFI302 User s Manual 2 14...
Page 46: ...DFI302 User s Manual 3 16...
Page 56: ...DFI302 User s Manual 4 10...
Page 60: ...DFI302 User s Manual 5 4...
Page 64: ...DFI302 User s Manual 6 4 Dimensions...
Page 82: ...DFI302 User s Manual 7 18...
Page 88: ...DFI302 User s Manual 8 6...
Page 92: ...DFI302 User s Manual 9 4...
Page 136: ...DFI302 User s Manual 10 44...
Page 162: ...DFI302 User s Manual 11 26...
Page 182: ...DFI302 User s Manual 12 20...
Page 216: ...DFI302 User s Manual 15 12...