Connecting External Sources
SMA America, LLC
122
SI5048U-TUS121440
Technical Description
Generator Interface ”234.07 GnSrtMod” = Manual; Generator Request Via
Sunny Island
Generator Interface ”234.07 GnSrtMod” = Autostart; Generator Request Via
Sunny Island
14.1.6 Limits and Power Adjustment
The voltage limits can be set using the ”234.01 GnVtgMin” and ”234.02 GnVtgMax” parameters
and the frequency limits for generator operation can be set using the ”234.05 GnFrqMin” and
”234.06 GnFrqMax” parameters. If the values are outside these permitted limits, the generator is
disconnected. Slightly narrower limits apply to generator connection.
1
Generator is requested via Sunny Island
2
Manual generator start
3
”Generator is running” detected, beginning of warm-up phase
4
Warm-up phase is completed, connection
5
Generator current limit
6
Minimum run time has expired
7
Current is reduced, battery absorption phase
8
Charging process is completed, request signal is disabled
9
Manual generator stop
10 Generator is disconnected
11 Stop time has expired
1
Generator started by Sunny Island
2
Generator start
3
Beginning of warm-up time
4
Warm-up time has expired
5
Generator is connected
6
Current limit
7
Minimum running time expired
8
Current is reduced, battery absorption phase
9
Charging process is completed, generator disconnection
10 Generator shut-off delay time expired, generator disconnection
11 Stop time has expired
Power-Dependent Generator Start
Warm-up times, minimum run times and shut-off delay times are also maintained for power
dependent generator starts.
System Voltage (AC)
The system voltage (AC) depends on the generator voltage when the generator is running.