SMA America, LLC
Parameter lists
Technical Description
SI5048U-TUS121440
165
233# Grid Start
No. Name
Description
Display value
Explanation
Default
value
01
GdSocTm1Str
SOC limit for
switching on the
grid for time 1
40 %
02
GdSocTm1Stp
SOC limit for
switching off the
grid for time 1
80 %
03
GdSocTm2Str
SOC limit for
switching on the
grid for time 2
40 %
04
GdSocTm2Stp
SOC limit for
switching off the
grid for time 2
80 %
05
GdTm1Str
Time 1 for grid
request in hours,
minutes and
seconds.
Begin time 1, end
time 2.
06
GdTm2Str
Time 2 for grid
request in hours,
minutes and
seconds.
Begin time 2, end
time 1.
07
GdPwrStr
Grid request
starting capacity
4.0 kW
08
GdPwrStp
Grid request
disconnection
power limit
2.0 kW
09
GdStrChrgMod Charging start
upon grid
connection
Off
Off
Equal
Full
Full charge
Equal
Equalize charge
Both
Full and equalization
charge