SMA America, LLC
19 Parameter Lists
Technical description
SI4548_6048-US-TB_en-13
173
233# Grid Start
No. Name
Description
Value
Explanation
Default
value
01
GdSocTm1Str
SOC limit for
switching on the
grid for time 1
40%
02
GdSocTm1Stp
SOC limit for
switching off the
grid for time 1
80%
03
GdSocTm2Str
SOC limit for
switching on the
grid for time 2
40%
04
GdSocTm2Stp
SOC limit for
switching off the
grid for time 2
80%
05
GdTm1Str
Time 1 for grid
request in hours,
minutes and
seconds
Begin time 1,
end time 2
06
GdTm2Str
Time 2 for grid
request in hours,
minutes and
seconds
Begin time 2,
end time 1
07
GdPwrStr
Grid request
starting capacity
4.0 kW
08
GdPwrStp
Grid request
disconnection
power limit
2.0 kW
09
GdStrChrgMod Charge start when
connecting to the
grid
Off
off
Equal
Full
Full charge
Equal
Equalization
charge
Both
Full and
equalization
charge
Summary of Contents for Sunny Island 4548-US