19 Parameter Lists
SMA America, LLC
174
SI4548_6048-US-TB_en-13
Technical description
234# Generator Control
No. Name
Description
Value
Explanation
Default
value
01
GnVtgMin
Minimum
generator voltage
80 V
02
GnVtgMax
Maximum
generator voltage
150 V
03
GnCurNom
Nominal generator
current
30 A
04
GnFrqNom
Generator nominal
frequency with
nominal load
60 Hz
05
GnFrqMin
Minimum
generator
frequency
54 Hz
06
GnFrqMax
Maximum
generator
frequency
66 Hz
07
GnStrMod
Generator
interface
Manual
Manual
Autostart
Autostart
Automatic
GenMan
SMA generator
management box
08
GnOpTmMin
Minimum run time
of the generator
15 min
09
GnStpTmMin
Minimum stop time
of the generator
15 min
10
GnCoolTm
Cooling time of the
generator
5 min
11
GnErrStpTm
Stop time of
generator in case
of errors
1 h
12
GnWarmTm
Warm-up time
60 sec
13
GnRvPwr
Generator reverse
power (active
power)
100 W
14
GnRvTm
Permissible time for
reverse power/
reverse current
30 sec