8 Power Control
SMA Solar Technology AG
64
SCCP-JP-BA-A4-en-12
User Manual
You can set the procedure for reactive power control in the operating state "Q at Night" via the parameter
QoDQ-VArMod
. Use this parameter to configure how the specifications of the grid operator are to be received and
implemented.
There are seven different modes for reactive power control. The default value for this parameter is
Off
.
Procedure:
1. Ensure that the Sunny Central is in the operating state "Stop".
2. Log into the user interface.
3. Change the parameter
QoDQ-VArMod
4. Change any parameters associated with the selected mode.
5. Use the parameter
PwrMonErrMod
to select the desired inverter behavior in the absence of setpoint specifications
as follows:
6. If
SubVal
has been selected, enter the proxy values for normal feed-in operation and for operation outside of normal
feed-in operation, as follows:
Mode
Description
Off
The reactive power setpoint is limited to 0 kVAr.
VArCtlCom
The reactive power setpoint is received via the Power Reducer Box or the Power Plant Controller.
VArCnst
The parameter
QoDQ-VAr
is used to set the reactive power setpoint in kVAr.
VArCnstNom
The parameter
QoDQ
-
VArNom
is used to set the reactive power setpoint as a percentage
relative to
Pmax
.
VArCnstNomAnIn The reactive power setpoint is imported via an analog input. The analog value is converted into a
reactive power setpoint.
VArCtlVol
The reactive power is set as a function of the line voltage.
VArCtlVolHystDb
The provision of reactive power helps perform voltage-stabilizing measures in the event of
overvoltage or undervoltage. The parameterization is carried out by means of a reactive power/
voltage characteristic curve.
VArCtlVolHysDbA The provision of reactive power helps perform voltage-stabilizing measures in the event of
overvoltage or undervoltage. The parameterization is carried out by means of a reactive power/
voltage characteristic curve and an activation power.
Parameter block
The parameter
QoDQ-VarMod
can only be changed in the operating state "Stop". The entry will not be accepted
in any other operating state.
Setting
Description
LastVal
If specified via communication: utilization of the last value received. In case of analog
setpoints: utilization of the last valid mean value.
SubVal
Utilization of the configured proxy values. SMA recommends use of the proxy values when
setpoint specifications are effected via analog signals.
Parameters
Description
Q-VArSubValRun
Proxy value for the reactive power setpoint in feed-in operation
PF-PFSubValRun
Proxy value for the displacement power factor in feed-in operation
PF-PFExtSubValR
Proxy value for the excitation of the displacement power factor in feed-in operation
Q-VArSubVal
Proxy value for the reactive power setpoint outside of feed-in operation