dFac-Max
Maximum "grid frequency change" before the grid monitoring
system disconnects the device from the grid.
dZac
Maximum "grid impedance change" before the grid monitoring
system disconnects the device from the grid.
E_Total
Total energy yield for the inverter. This change may be
necessary when you replace the Sunny Boy and want to use the
data stored in the old device.
Fac-delta-
Maximum frequency, above (Fac-delta+) and below (Fac-delta-)
the grid frequency of 50 or 60 Hz, before the grid monitoring
system disconnects the device from the grid.
Fac-delta+
Fac-Pderating
Frequency-dependent output limitation.
Fac-Tavg
Averaging time of grid frequency measurement.
h_Total
Total hours of operation for the inverter. The changes may be
necessary when you exchange your Sunny Boy and want to use
the data from the old device.
I-NiTest
Setting the impulse for impedance monitoring. This parameter
only functions when the Sunny Boy is deactivated (disconnected
on the AC side) or in "Stopp" mode.
Speicherfunktion
Default parameter: returns all parameters to the factory settings.
Reset Betriebsdaten: returns all user level parameters to the
factory settings.
Reset Fehler: resets a permanent error.
Speicher/Storage
Permanent: modified parameters are stored in the EEPROM and
can be used even when the Sunny Boy has been restarted.
Volatil: prevents the parameters being stored in the EEPROM,
the parameters are only stored until the next restart.
T-Start
The period the Sunny Boy waits after all switch-on conditions
have been satisfied.
T-Stop
The period the Sunny Boy waits before disconnecting from the
grid.
Uac-Min
Lower (Uac-Min) and upper (Uac-Max) limits of the allowable
AC voltage (stand-alone grid recognition), before the grid
monitoring system disconnects the device from the grid.
Uac-Max
Uac-Tavg
Averaging time for measuring grid frequency
Name
Explanation
Summary of Contents for Sunny Boy SB 2500
Page 2: ......
Page 6: ...Explanation of the Symbols Used SMA Technologie AG Page 6 SB25_30 11 SE0307 Installation Guide...
Page 10: ...Safety Instructions SMA Technologie AG Page 10 SB25_30 11 SE0307 Installation Guide...
Page 20: ...Installation Requirements SMA Technologie AG Page 20 SB25_30 11 SE0307 Installation Guide...
Page 62: ...The Communication Interface SMA Technologie AG Page 62 SB25_30 11 SE0307 Installation Guide...
Page 65: ......