Installation requirements
SMA
Technologie AG
Page 18
SB1700-11:SE2006
Installation Guide
The Sunny Boy 1700 is designed for operation on 230 V grids and works at grid
voltages of 198 V to 260 V at 49.8 Hz to 50.2 Hz.
The Sunny Boy 1700 is equipped with an automatic 50 Hz / 60 Hz utility frequency
detection. It can therefore be connected to a 50 Hz or 60 Hz utility without any
further configuration changes. Pay attention to the local utility regulations in any
case.
Limit values for AC output
Voltage range
198 V ... 260 V
Frequency range
49.8 Hz ... 50.2 Hz
Voltage range
(without "MSD" independent
disconnection device)
180 V ... 260 V
Frequency range
(without "MSD" independent
disconnection device)
45.5 Hz ... 54.5 Hz