13 Technical Data
SMA Solar Technology AG
Operating manual
SBxx-1AV-41-BE-en-12
102
SB3.0-1AV-41
SB3.6-1AV-41
SB4.0-1AV-41
Power factor at rated
power
1
1
1
Displacement power
factor cos φ, adjustable
0.8 overexcited to 0.8
underexcited
0.8 overexcited to 0.8
underexcited
0.8 overexcited to
1
to
0.8 underexcited
Feed-in phases
1
1
1
Phase connection
1
1
1
Surge category in ac-
cordance with
IEC 60664-1
III
III
III
* Depending on the configured country data set
Efficiency
SB3.0-1AV-41
SB3.6-1AV-41
SB4.0-1AV-41
Maximum efficiency,
η
max
97.0 %
97.0 %
97.0 %
European weighted ef-
ficiency, η
EU
96.4 %
96.5 %
96.5 %
13.1.2 Sunny Boy 5.0 / 6.0
DC input
SB5.0-1AV-41
SB6.0-1AV-41
Maximum PV array power
7500 Wp
9000 Wp
Maximum input voltage
600 V
600 V
MPP voltage range
125 V to 500 V
125 V to 500 V
Rated input voltage
365 V
365 V
Minimum input voltage
100 V
100 V
Initial input voltage
125 V
125 V
Maximum input current, input A
15 A
15 A
Maximum input current, input B
15 A
15 A
Maximum input current per
string, input A
15 A
15 A
Maximum input current per
string, input B
15 A
15 A
Maximum short-circuit current,
input A*
20 A
20 A