Terminal
Cable requirements
Analog setpoint
• 2 x 4 mm
2
• The cables used must be shielded against 600 V.
Remote shutdown
• 2 x 4 mm
2
• The cables used must be shielded.
AC cable
• Connection with outer-cone angle plug type C
Communication interface
Connection with Ethernet cables
• The cables must be shielded and pair-twisted.
• The cables must be at least category 5 (CAT 5).
• Maximum cable length: 100 m
or
Connection of optical fibers with optical fiber pigtail*
• 50 μm multi-mode optical fiber
• Two optical fiber pigtails with subscriber connector
or
Connection of optical fibers with subscriber connector*
• Two subscriber connectors
Grounding conductor
Minimum 1 x 50 mm
2
to maximum 2 x 95 mm
2
* optional
5.3
Q at Night
The MV Power Station can support the grid quality by feeding in reactive power. The inverters can feed in reactive
power up to a displacement power factor of 0.9 during feed-in operation. This corresponds to a reactive power of
43.5% of the nominal power.
5 Electrical Connection
SMA Solar Technology AG
Transportation and Installation Requirements
35
MVPS22JP-TA-en-20