The MV Power Station is lifted by the four corner castings using a container crossbeam with chain sling. It can be lifted
by the top or bottom corner castings. The angle between chain sling and the ground must be greater than 45°.
Figure 7: Attachment of the support feet during unloading of the MV Power Station at the mounting location
Attaching the Support Feet During Unloading
The MV Power Station must be mounted on six support feet. The support feet can be found in the accessory kit in the
medium-voltage switchgear compartment. The support feet must be fitted to the MV Power Station before it is placed
on the foundation. To attach the support feet, open-end wrenches with a width across flats of 30 mm and 36 mm are
required.
Attaching the support feet of the MV Power Station
To attach the support feet to the MV Power Station, you can set the MV Power Station down for a short while on
temporary platforms (for example, crane support plates). For the assembly of the support feet, the platforms must
be at least 450 mm high.
The space underneath the MV Power Station serves several purposes and must not be blocked by any object other
than the oil spill containment:
• Escape of pressure from the medium-voltage switchgear in case of electric arcs
• Easy insertion of cables
• Protection from minor flooding
• Heat dissipation of the inverters
The clearance between the mounted MV Power Station and the ground must be at least 350 mm.
3 Transport and Mounting
SMA Solar Technology AG
Transportation and Installation Requirements
15
MVPS22JP-TA-en-20