Event number
Message, cause and corrective measures
10353
Webconnect error: registration of the SIP registry has not responded
SIP Registrar not fully available.
Corrective measures:
• Ensure that the network cable at the inverter is correctly connected.
• Check the configuration of the router.
10502
Active power limited AC frequency
The inverter has reduced its power due to a too-high power frequency to en-
sure grid stability.
Corrective measures:
• If possible, check the power frequency and observe how often
fluctuations occur. If fluctuations occur frequently and this message is
displayed often, contact the grid operator and request approval to
change the operating parameters of the inverter. If the grid operator
gives his approval, discuss any changes to the operating parameters
with Service (see Section 15 "Contact", page 96).
10901
Start self-test [xx]
The self-test is running.
10902
Uac RPro [xxx] V
Preliminary result of the self-test
10903
Uac Max [xxx] V
Preliminary result of the self-test
10904
Uac Min [xxx] V
Preliminary result of the self-test
10905
Uac Min Fast [xxx] V
Preliminary result of the self-test
10906
Fac SwMax [xxx] Hz
Preliminary result of the self-test
10907
Fac SwMin [xxx] Hz
Preliminary result of the self-test
10908
Fac Max [xxx] Hz
Preliminary result of the self-test
10909
Fac Min [xxx] Hz
Preliminary result of the self-test
10910
Disconn. threshold [xxx] [xx]
Preliminary result of the self-test
12 Troubleshooting
SMA Solar Technology AG
Operating Manual
79
SB30-50-1AV-40-BE-en-10