Operation
5.1.
Alarms
Mains
: signalled locally by a green LED and remotely by dry contact with delay (failsafe).
If
the mains is not present > LED will go out
Charger
: signalled locally by a green LED and remotely by dry contact with delay (failsafe).
If
the mains fuse is blown or not present.
If
the mains is <98 V or 195 V at 100-150 W.
If
the product is out of service. > LED will go out
Battery
: signalled locally by a green LED and remotely by dry contact with delay (failsafe).
If
the battery is not present:
The battery test is performed in the following manner: every 30 seconds for the first 20 minutes
after commissioning: every 15 minutes after the first 20 minutes. If a fault is detected, the test is
performed every 30 seconds up to 20 minutes after the fault disappears.
Signalled locally by LED not illuminated.
If
the battery voltage < 1.85 V/cell
±3 %
, signalled locally by a flashing orange LED.
5.2.
Available equipment
Battery current limitation:
The charge current is controlled and electronically limited to In at 75 W and to 75 % of In at 100-600 W.
Battery low voltage cut-out:
The cut-out threshold is 1.8 V/cell
±3 %
.
The element causing the cut-out will be in the + position.