24
1.
General information
1.1.
Correspondence table
75 W
100 W
150 W
200 W
300 W
400 W
600 W
24 V
3 A
4 A
6 A
8 A
12 A
16 A
24 A
The currents (
In
) shown are at rated output power.
1.2.
Environmental specifications
Operating temperature:
-5 °C to +40 °C at 100 % charge.
-5 °C to +50 °C at 75 % charge.
-5 °C to +50 °C at 100 % charge for 75 W to 100 W.
Storage temperature: -25 to +85 °C.
Relative humidity: 20 to 95 %.
1.3.
Electrical input and output specifications
1.3.1
Network input
-
single-phase voltage: 98 V to 264 V except 100-150 W: 195 V to 264 V.
-
frequency: 47 to 63 Hz.
-
class I.
-
neutral systems: TT, TN, IT.
75 W
100 W
150 W
200 W
300 W
400 W
600 W
Primary current at mains
= 98 V
1 A
-
-
3 A
4 A
6 A
8 A
Primary current at mains
= 195 V
0.5 A
0.75 A
1 A
1.5 A
2 A
3 A
4 A
Circuit breaker to be provided upstream: D curve
1.3.2 Output
-
Rated voltage: 24 V.
-
Floating voltage set at half-load and at 25 °C: 27.2 V
±0.5 %.
-
adjustment range *: 23-29 V.
* In power supply mode without battery exclusively. All use of the adjustment range in charger mode with
the battery will void the product's warranty.
-
output current:
75 W
100 W
150 W
200 W
300 W
400 W
600 W
Load1 Output
3 A
4 A
6 A
8 A
12 A
16 A
24 A
Load2 to 6 outputs
4 A
4 A
4 A
4 A
4 A
4 A
4 A
Summary of Contents for SANTE