SLAT SANTE Operating Instructions Manual Download Page 23

23 

 
 

Congratulations, 

You have just acquired a Santé emergency power supply by SLAT, and we thank you for your choice. 
This manual includes instructions for the installation, commissioning and maintenance of this equipment. 
In order for the equipment to work properly, we recommend that these instructions be followed very carefully. 
 

...

 

 

 

Safety precautions 

 
This equipment is designed to be connected to the 230 V public distribution network. 
To avoid any risk of electric shock, all 

INTERVENTIONS

 must be carried out with the equipment 

SWITCHED OFF

 

(upstream two-pole circuit-breaker open). 
Interventions with the equipment switched on are authorized only when it is impossible to switch the equipment off. 
The operation must only be performed by qualified personnel. 
 
 

Standards, directives and protection of the environment and public health 

 
All  products  of  the  Santé  range  are  compliant  with  LV  and  EMC  directives  (immunity  and  emission).  They  are 
compliant with standards: 

 

EN 60950-1 (2006) + A11 (2009) + A1 (2010) + A12 (2011) + A2 (2013) (TBTS class) 

 

EN 61000-6-1(2007), EN 61000-6-2 (2005), EN 61000-6-3 (2007), EN 61000-6-4 (2007) + A1 (2011)  

 

EN 55022 (2006) + A1 (2007) class B 

 

UL1950 for components. 

 
SLAT is ISO 14001 certified since 2008. 
SLAT manufactures all its products in accordance with RoHS and WEEE environmental directives. 
SLAT recycles its products at the end of their service life through its recycling programme. 
 
 

 
 
 
 
 

 
 

Warranty 

 
Our  warranty  is  three  years  from  the  date  of  delivery  (ex-works).  It  is  strictly  limited  to  reimbursement  or 
replacement (at our discretion and without compensation of any sort) of parts recognised as faulty by our services, 
following return of the product to our premises at the buyer's expense. The replacement or repair of equipment is 
possible  only  on  our  premises.  In order  to  allow  our  customers  to benefit  from  the  latest  technical  improvements, 
SLAT  reserves  the  right  to  make  all  necessary  modifications  to  its  products.  The  battery  is  not  included  in  the 
warranty. 
 
 
 
 

 

 

Summary of Contents for SANTE

Page 1: ...Code 180100023Ba NDU NOT100023Ba Edition 1016 NOTICE D UTILISATION P1 BEDIENUNGSANLEITUNG S11 OPERATING INSTRUCTIONS P21 NOTICE D UTILISATION Sant 75W 600W...

Page 2: ...de sortie 4 2 Installation de votre quipement 5 2 1 Fixation et dimensions des coffrets dim LxHxP mm 5 2 2 Batteries 5 3 Raccordement 6 3 1 Plan de raccordement 6 3 2 Sp cifications de raccordement 7...

Page 3: ...directives BT et CEM immunit et mission Ils sont conformes aux normes EN 60950 1 2006 A11 2009 A1 2010 A12 2011 A2 2013 Classe TBTS EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 EN 61000 6 4...

Page 4: ...as e 98V 264V sauf 100 150W 195V 264V fr quence 47 63Hz classe I r gimes de neutre TT TN IT 75W 100W 150W 200W 300W 400W 600W Courant primaire secteur 98V 1A 3A 4A 6A 8A Courant primaire secteur 195V...

Page 5: ...nsions des coffrets dim LxHxP mm C24 Dim 322x248x126mm IP 30 C48 Dim 425x345x120mm IP30 C85 Dim 408x408x224mm IP31 C180 Dim 505x610x430mm IP31 2 2 Batteries Vous trouverez le plan d int gration et de...

Page 6: ...ts fusibl s 400 600W Le collier fourni avec tous les produits permet la fixation du c ble secteur au niveau du bornier secteur Attention les ouvertures pr vues dans le coffret doivent tre utilis es Ne...

Page 7: ...75 150W quip es du fusible r armement automatique raccorder les fils batterie sur le bornier mais ne pas raccorder les bornes de la batterie Apr s avoir effectu les raccordements lectriques secteur u...

Page 8: ...RTC s curit positive Si la batterie est absente Le test batterie s effectue de la mani re suivante toutes les 30s pendant les 20 premi res minutes apr s la mise en service toutes les 15min apr s les...

Page 9: ...la batterie d origine par une batterie de type incorrect peut engendrer un risque d explosion Les batteries usag es doivent tre mises au rebut conform ment aux obligations de recyclage des mat riaux 7...

Page 10: ...ilisation Si la batterie ne prend pas le relais apr s un d faut secteur Contr ler la tension aux bornes de la batterie Contr ler le fusible batterie Contr ler la tension sur les bornes utilisation Si...

Page 11: ...11 NOTICE D UTILISATION P1 BEDIENUNGSANLEITUNG S11 OPERATING INSTRUCTIONS P21 BEDIENUNGSANLEITUNG Sant 75 W bis 600 W...

Page 12: ...en 14 2 Montage der Stromversorgung 15 2 1 Befestigung und Abmessungen der Geh usek sten Abm LxHxT mm 15 2 2 Batterien 15 3 Anschluss 16 3 1 Anschlussplan 16 3 2 Spezifizierung der Anschl sse 17 4 Inb...

Page 13: ...aus der Baureihe SANTE halten die NS Richtlinien und EMV Normen bzgl St rfestigkeit und Emission ein Sie entsprechen den Normen EN 60950 1 2006 A11 2009 A1 2010 A12 2011 A2 2013 Klasse TBTS EN 61000 6...

Page 14: ...0 W 195 V bis 264 V Frequenz 47 bis 63 Hz Klasse I Sternpunktbetrieb TT TN IT 75 W 100 W 150 W 200 W 300 W 400 W 600 W Prim rstrom Netz 98 V 1 A 3 A 4 A 6 A 8 A Prim rstrom Netz 195 V 0 5 A 0 75 A 1 A...

Page 15: ...Abmessungen der Geh usek sten Abm LxHxT mm C24 Dim 322x248x126mm IP 30 C48 Dim 425x345x120mm IP30 C85 Dim 408x408x224mm IP31 C180 Dim 505x610x430mm IP31 2 2 Batterien Das Einbau und Verkabelungsschem...

Page 16: ...e mit 5 Sicherungsausg ngen 400 600 W Mit der mitgelieferten Schelle kann das Netzkabel in H he der Netzklemmleiste befestigt werden Achtung Die im Geh use vorgesehenen ffnungen m ssen verwendet werde...

Page 17: ...150 W mit selbstr ckstellender Sicherung Schlie en Sie die Dr hte der Batterie an die Klemmleiste an aber schlie en Sie die Batterieklemmen noch nicht an Nachdem die elektrischen Anschl sse hergestell...

Page 18: ...NO NC Kontakt elbst sicher angezeigt Wenn keine Batteriespannung anliegt Der Batterietest wird wie folgt ausgef hrt alle 30 s w hrend der ersten 20 min nach Inbetriebnahme alle 15 min nach den ersten...

Page 19: ...atterie eines anderen Typs kann zur Explosion f hren Verbrauchte Batterien m ssen gem den Recycling Bestimmungen entsorgt werden 7 Sicherungen 24 V 3 A 24 V 4 A 24 V 6 A 24 V 8 A 24 V 12 A 24 V 16 A 2...

Page 20: ...cht ihre Aufgabe bernimmt Kontrollieren Sie die Spannung an den Batterieklemmen Kontrollieren Sie die Batteriesicherung Kontrollieren Sie die Spannung an den Verbraucherklemmen Wenn die Kontrollleucht...

Page 21: ...21 NOTICE D UTILISATION P1 BEDIENUNGSANLEITUNG S11 OPERATING INSTRUCTIONS P21 OPERATING INSTRUCTIONS Sant 75 W to 600 W...

Page 22: ...cifications 24 2 Installation of your equipment 25 2 1 Mounting and cabinet dimensions dim LxHxW mm 25 2 2 Batteries 25 3 Connection 26 3 1 Connection diagram 26 3 2 Connection specifications 27 4 Com...

Page 23: ...LV and EMC directives immunity and emission They are compliant with standards EN 60950 1 2006 A11 2009 A1 2010 A12 2011 A2 2013 TBTS class EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 EN 610...

Page 24: ...100 150 W 195 V to 264 V frequency 47 to 63 Hz class I neutral systems TT TN IT 75 W 100 W 150 W 200 W 300 W 400 W 600 W Primary current at mains 98 V 1 A 3 A 4 A 6 A 8 A Primary current at mains 195...

Page 25: ...abinet dimensions dim LxHxW mm C24 Dim 322x248x126mm IP 30 C48 Dim 425x345x120mm IP30 C85 Dim 408x408x224mm IP31 C180 Dim 505x610x430mm IP31 2 2 Batteries A battery integration drawing and wiring sche...

Page 26: ...5 output board fuse protected 400 W 600 W The cable tie included with all the products allows the mains cable to be secured to the mains terminal strip Important the openings provided in the cabinet m...

Page 27: ...tery fuse or for 75 W to 150 W boards equipped with an automatic reset fuse connect the battery wires to the terminal strip but do not connect the battery terminals After the electrical connections ar...

Page 28: ...ttery is not present The battery test is performed in the following manner every 30 seconds for the first 20 minutes after commissioning every 15 minutes after the first 20 minutes If a fault is detec...

Page 29: ...y of incorrect type may result in an explosion hazard Used batteries must be disposed of in compliance with recycling requirements 7 Fuse protections 24 V 3 A 24 V 4 A 24 V 6 A 24 V 8 A 24 V 12 A 24 V...

Page 30: ...ompatibility of your load If the battery does not take over after a mains fault Check the voltage on the battery terminals Check the battery fuse Check the voltage on the load terminals If the indicat...

Page 31: ...31...