27
Core use table
C24-C48
C38-C85
C180
75 W
None
None
-
100-150 W
OUTPUT CORE to be installed
OUTPUT CORE pre-installed
-
200-300 W
OUTPUT CORE to be installed
OUTPUT CORE pre-installed
OUTPUT CORE pre-installed
400-600 W
MAINS CORE + REPORTS
CORE +
OUTPUT CORE to be installed
-
MAINS CORE + REPORTS
CORE +
OUTPUT CORE pre-installed
3.2.
Connection specifications
75 W
100-150 W
200-300 W
400-600 W
Mains
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
Batteries
2.5 mm²
6 mm²
6 mm²
10 mm²
Load (motherboard)
2.5 mm²
6 mm²
6 mm²
10 mm²
Load (multiple outlet board)
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
Alarm reports* (unpluggable)
1.5 mm²
1.5 mm²
1.5 mm²
1.5 mm²
4.
Commissioning
Open the battery fuse, or for 75 W to 150 W boards equipped with an automatic reset fuse: connect the battery
wires to the terminal strip, but do not connect the battery terminals.
After the electrical connections are made (mains, loads and batteries).
1. Close the upstream mains circuit-breaker.
2. Check the load output voltage. The LED on the motherboard turns red.
3. Close the battery fuse or connect the battery terminals for 75 W to 150 W boards.
4. Check that the LED confirming correct motherboard operation is illuminated:
a. all OK: green,
b. mains fault: orange,
c. battery or charger fault, or load not present: red (this fault takes priority over a mains fault).
5. Connect the ground wire and the wire ribbon (if equipped).
6. Close the cover.
Your apparatus is in operation when the 3 green LEDs, corresponding to the mains, charger and battery are
illuminated.